Recharge refrigerant
When the outdoor valve is shut,fill the refrigerant from the access hole at the gas and liquid sides.
If the required filling is impossible,open all the gas and liquid valves,then slightly shut the gas valve,
run the compressor and fill the refrigerant from the access hole at the gas side.Now adjust the gas valve
to control the refrigerant flow,which will be gasified during absorption by the system.
If there is insufficient refrigerant in the system caused by leaks,refill it after the remaining refrigerant
is recollected.
Open all valves
Open all the valves of the outdoor unit.
Heat isolation of the pipes
Separate isolation should be made for the liquid and gas pipes.
Materials used for the pipe isolation at the gas side must withstand above 120 C temperature.
The quantity of the refrigerant t be refilled on the site=Actual length of liquid tube x quantity of
refrigerant to be refilled for per meter of liquid pipe.