Outdoor unit:
Ta- Ts ≥2℃, run at cooling mode
Ta- Ts <2℃, the compressor will run at 34Hz and 60Hz in turn, and keeps 6 minutes at 34Hz; 10 minutes at
60Hz.
Ta < 1 5℃, Ts(minimum)=16℃, the compressor will run fitfully, run for 10 minutes, stop for 6 minutes; and
they will run in turn.
8.2.5 Heating operation
Outdoor unit:
4-way valve electrified
2-way valve shutoff
if the unit shutoff in heating mode or the state changes, the 4-way valve will be not electrified 1 minute
and 50 seconds later.
(1) Fan motor
Ta>16.5℃ Low speed
Ta< 1 3℃ High speed
Tolerance: 3.5℃
(2) Compressor frequency
The compressor frequency changing procedure refers to APPENDIX 1.
Frequency limited condition of ambient temperature:
Ta≥28℃ Max. frequency 60Hz
22℃≤T≤28℃ Max. frequency 72Hz
16℃≤T≤22℃ Max. frequency 84Hz
4℃≤T≤16℃ Max. frequency 108Hz
T≤4℃
Max. frequency 120Hz
(3) In heating mode, indoor heat exchanger overload protection
Te< 4 8℃ no limited
54℃≤Te< 5 8℃ frequency not change
Te> 6 3℃ outdoor fan motor stops
Te< 6 0℃ outdoor fan motor resumes
72℃ unit shutoff; 52℃ unit resumes.
(4) Current protection
current<1.882V, no limited
2.023V≤current<2.201V, frequency not change
2.32V, fan motor stops
2.25V, fan motor works
current>2.556V, unit shutoff.
Note: The current limitation for different models, you can choose it due to the different distributing voltage
of the hardware current detecting circuit.
(5) Compressor overheat protection
Tc(compressor temperature)< 97℃, no limited
103℃≤Tc<108℃, frequency not change
>a__WcU[S^ <[c >a`V[e[a`Wc