21
                                                    Domestic air conditioner
HSU-09/12RS03/R2(SDB)
Function and control
5.2.2 Outdoor fan control 
 
Compressor startup within 3min ,outdoor fan speed control as follows: 
Outdoor 
Temperature
 ī ı
Cooling/
Dehumidification
  
Heating
  
fter compressor runs 3min ,outdoor fan speed control as follows: 
Cooling/ Dehumidification: 
 Compressor Operation Frequency˄Hz˅  ī ı
7DR˄ć˅
İ   
28ī   
ı8
Heating: 
Compressor Operation Frequency˄Hz˅  ī ı
7DR˄ć˅
İ   
ī   
ı 
Compressor shutdown and outdoor fan residual heat blow process 
When compressor shuts down in cooling mode, outdoor fan automatically jumps to low speed and 
blows residual heat for 30s and stop.
5.2.3 Four-way Valve Control 
Defrosting Four-way Valve Controlˈ(please see defrosting process for details) 
Time sequence of the defrosting operation is as follows: 
Four-way Valve Work Status in Other Modes: 
In heating mode, four-way valve is on. If compressor is off or is switched to non-heating mode, 
four-way valve ensures that it is off at least 3 minutes after compressor shuts down. 
5.2.4 Outdoor Defrosting Control 
Defrosting Mode Entry Conditions 
The unit will enter defrosting mode when compressor starts up and operates for 1 minutes 
continuously in heating mode or after compressor runs for an accumulated time of 30 minutes (Upon 
completion of defrosting or when switched to cooling mode, compressor accumulated operation time 
will be cleared) and when 2 minutes’ continuous checking by defrosting sensor TE (check frosting 
condition of outdoor unit heat exchanger) and outdoor ambient temperature sensor TA meets the 
following conditions: