                                                    Domestic air conditioner
HSU-09/12RS03/R2(SDB) Service Diagnosis
7.4.3 IPM protection 
Outdoor display     
LED1  flash  2  times
Method of       
IPM protection is detected by checking the compressor running condition and so on
Malfunction       
Detection 
Malfunction      Ŷ 
The system leads to IPM protection due to over current
Decision Ŷ 
The compressor faulty leads to IPM protection 
Conditions       Ŷ
  circuit component of IPM is broken and led to IPM protection
Supposed         Ŷ
  IPM protection dues to the compressor faulty 
Causes Ŷ 
IPM protection dues to faulty PCB of IPM module   
Ƶ
Compressor wiring disconnected 
Troubleshooting    
* Caution   
Be sure to turn off power switch before connect or disconnect connector,      or 
else parts damage may be occurred. 
7.4.4 The IPM and outdoor PCB don’t communicate or Related Abnormality 
outdoor display    LED1 flash  4 times     
Indoor Display   
F3
Method of  Communication is detected by checking the IPM module and the outdoor PCB 
Malfunction       
Detection
Malfunction 
Ƶ
The outdoor PCB broken leads to communication fault
Decision
 
Ƶ
The IPM module broken leads to communication fault
Conditions 
Supposed
Ƶ
The outdoor PCB is broken
Causes 
Ƶ
The IPM module is broken       
Electrify the machine again and turn it on
with the remote controller,If malfunctions
are reported before or upon the
compressor being started up, 
IPM Module is damaged and 
needs replacing. 
1ᇬThe system may have been over or under charged with gas, which can be judged through the pressure of the 
measuring system.   
2ᇬThe shaft of compressor is seized and the compressor needs replacing. 
<(6
12
The compressor is started normally, but 
malfunctions are reported after it has run for 
some time.   
Malfunction unsolved