www.haiwell.com Haiwell PLC - Analog Module User Manual
10. Module Parameter Table
(CR code is corresponding to the Modbus register address)
4-channel analog module parameter table
Note: CR code is corresponding to the Modbus register address, the ray parts are read-only ,the white parts are readable and
writable.
Low byte for module code, and high byte for module version number.
Communication protocol: The low 4-bit of the low byte: 0 - N,8,2 For RTU, 1 - E,8,1 For RTU, 2 - O,8,1 For RTU, 3 - N,7,2 For ASCII, 4 -
E,7,1 For ASCII, 5 - O,7,1 For ASCII, 6 - N,8, 1 For RTU
The high 4-bit of the low byte: 0 – 2400, 1 – 4800, 2 – 9600, 3 – 19200, 4 – 38400, 5 – 57600, 6 - 115200
Default IP address: 192.168.1.111
High byte subnet mask (b3~b0,1 indicates 255, 0 indicates 0, for example subnet mask 255.255.255.0, b3~b0=1110), low byte reserved
Error code: 0-Normal, 1-Illegal firmware identity, 2-Incomplete firmware, 3-System data access exception, 4-No external 24V power
supply
input channel 1 input value
input channel 2 input value
input channel 1 signal type, note 2
input channel 2 signal type, note 2
channel 1 signal type, note 2
channel 1 signal type, note 2
Use the engineering value mark, note 6
channel 2 signal type, note 2
channel 2 signal type, note 2
input channel 1 engineering lower limiting value
channel 3 signal type, note 2
channel 3 signal type, note 2
input channel 2 engineering lower limiting value
channel 4 signal type, note 2
channel 4 signal type, note 2
input channel 1 engineering upper limiting value
Use the engineering value mark, note 6
Use the engineering value mark, note 6
input channel 2 engineering upper limiting value
channel 1 engineering lower limiting
value
channel 1 engineering lower limiting
value
input channel 1 sampling frequency, note 1
channel 2 engineering lower limiting
value
channel 2 engineering lower limiting
value
input channel 2 sampling frequency, note 1
channel 3 engineering lower limiting
value
channel 3 engineering lower limiting
value
input channel 1 zero point correction value
channel 4 engineering lower limiting
value
channel 4 engineering lower limiting
value
input channel 2 zero point correction value
channel 1 engineering upper limiting
value
channel 1 engineering upper limiting
value
Channel 1~2 input disconnection alarm, note 5
channel 2 engineering upper limiting
value
channel 2 engineering upper limiting
value
output channel 1 output value
channel 3 engineering upper limiting
value
channel 3 engineering upper limiting
value
output channel 2 output value
channel 4 engineering upper limiting
value
channel 4 engineering upper limiting
value
output channel 1 signal type, note 2
channel 1 sampling frequency, note 1
power-off output mark, note 8
output channel 2 signal type, note 2
channel 2 sampling frequency, note 1
channel 1 power-off output value
Use the engineering value mark, note 6
channel 3 sampling frequency, note 1
channel 2 power-off output value
output channel 1 engineering lower limiting value
Channel 4 sampling frequency, note 1
channel 3 power-off output value
output channel 2 engineering lower limiting value
channel 1 zero point correction value
channel 4 power-off output value
output channel 1 engineering upper limiting value
channel 2 zero point correction value
Channel indicator status, note 7
output channel 2 engineering upper limiting value
channel 3 zero point correction value
power-off output mark, note 8
channel 4 zero point correction value
output channel 1 power-off output value
Channel 1~4 input disconnection
alarm, note 5
output channel 2 power-off output value
output channel indicator, note 7
8-channel analog module parameter table
Note: CR code is corresponding to the Modbus register address, the gray parts are read-only, the white parts are readable and
writable.
Low byte for module code, and high byte for module version number.
Communication protocol: The low 4-bit of the low byte: 0 - N,8,2 For RTU, 1 - E,8,1 For RTU, 2 - O,8,1 For RTU, 3 - N,7,2 For ASCII, 4 -
E,7,1 For ASCII, 5 - O,7,1 For ASCII, 6 - N,8, 1 For RTU
The high 4-bit of the low bytes: 0 – 2400, 1 – 4800, 2 – 9600, 3 – 19200, 4 – 38400, 5 – 57600, 6 - 115200
Default IP address: 192.168.1.111
High byte subnet mask(b3~b0,1 indicates 255,0 indicates 0 , for example, subnet mask 255.255.255.0, b3~b0=1110), low byte Reserved
Error code: 0-Normal, 1-Illegally firmware identity, 2-Incomplete firmware, 3-System data access exception, 4-No external 24V power
supply
input channel 1 input value