Operation & Maintenance & Service Manual
CJUV/012009/rev1/EN
Parameter name: P04
Allowed values: 0 Both fans are shut off.
1 Exhaust fan only is on.
2 Makeup fan only is on.
3 Both fans are turned on.
Factory default: 0
AIRFLOW ALARM DELAY
This sets the maximum time allowed for the pressure switch to be closed in On mode. After this
delay (in seconds), the unit will sound the buzzer to alert the operator.
Parameter name: P05
Allowed values: 0 (off, never sounds alarm) to 999
Factory default: 30
REMOTE ON/OFF
Enables or disables the remote On/Off switch. If enabled, keypad On/Off no longer controls the unit
(except to program Low-level). When enabled, a remote closed contact will mean On, and an Open
contact will mean Off.
Parameter name: P06
Allowed values: 0 Disabled.
1 Enabled.
Factory default: 0
UV LAMP FAILURE DETECTOR
Enables or disables the UV Lamp Failure detector. If enabled, the unit will monitor the input when-
ever the UV Lamp output is supposed to be on.
Parameter name: P07
Allowed values: 0 Disabled.
1 Enabled.
Factory default: 1