23
Before staring Installation Operation Specifications
Register
address
(HEX)
Symbol
Description
Property
(R/W)
Setting range Unit
Initial
value
CH1 CH2
n : Number of
channel
121
(79)
221
(DD)
EV.1TY
Set event channel 1
type
R/W
None(OFF)
1:Deviation high limit
2: Deviation low limit
3. Deviation high/low limit
4: Within deviation scope
5: Deviation high limit (stand by)
6: Deviation low limit (stand by)
7. Deviation low/high limit (stand by)
8. Within deviation (stand by)
9:PV high limit
10: PV low limit
11: PV high limit (stand by)
12:PV low limit (stand by)
13: SV high limit
14: SV low limit
15: Loop break (LBA)
16: -
17: Run start (RUN)
18: Run/monitor mode
(READY)
19: FAIL
ABS 0(OFF)
122
(7A)
222
(DE)
EV.1VL
Event set value of event
channel 1
R/W EUS (0 ~ 100%) EU (0 ~ 100%) ℃ -
123(7B)
223(DF)
EV.1HY
Event channel 1, event hysteresis
R/W EUS (0 ~ 10%) ℃ -
124(7C)
~
144(90)
224(E0)
~
244(F4)
EV.2
~
EV.8
Set event channel
2~8 event type, set
value and hysteresis
R/W Same as event channel 1
145
(91)
245
(F5)
LBA
Set loop break
event time
R/W 0(OFF), 1~7200 Sec. 0(OFF)
146
(92)
246
(F6)
LBD
Set loop break event
dead band
R/W EUS (0 ~ 100%) ℃
EUS
(100%)
147
(93)
247
(F7)
EVSTOP
Set stop run at event
occurrence
R/W
0: continuous run
1: stop run
ABS
0
(continuous
run)
148
(94)
248
(F8)
HBC
Heater break
current value
R 1~50A A -
149
(95)
249
(F9)
HBA
Heater break current
value setting
R/W 0(OFF), 1.0~50.0A A 0(OFF)
150
(96)
250
(FA)
HB_HYS
Heater break
hysteresis setting
R/W 0.0~50.0 A 0.3
151
(97)
251
(FB)
PB Set proportional band R/W EUS (0 ~ 100%) ℃
EUS
(1%)
152
(98)
252
(FC)
TI Set integral time R/W 1 ~ 3600 Sec. 240
153
(99)
253
(FD)
TD Set differentiation time R/W 1 ~ 3600 Sec. 60
154
(9A)
254
(FE)
AR/AP
Heating control: Set 2
DOF PID ALPHA
Heating/Cooing
control: Anti reset
windup (ARW) setting
R/W
Heating control: 1~100
Heating/Cooing control: 0(AUTO), 50.0~200.0
ABS 0
155
(9B)
255
(FF)
MR Set Manual Reset R/W 0.0 ~ 100.0 % 0.0
156
(9C)
256
(100)
CT Set control cycle R/W 1 ~ 100 Sec.
RELAY :
30 sec.
SSR
: 2 sec.
157
(9D)
257
(101)
PO Set emergency output R/W 0.0 ~ 100.0 % 0
158
(9E)
258
(102)
HYS
Set hysteresis at
ON/OFF control
R/W EUS (0 ~ 10%) ℃
EUS
(0.2%)
159
(9F)
259
(103)
RO
Set output at stop,
monitor status
R/W 0.0 ~ 100.0 % 0
160
(A0)
260
(104)
RUP
Set SV increase
temperature at RAMP
control
R/W EUS (0 ~ 100%) ℃
EUS
(0%)
161
(A1)
261
(105)
RDN
Set SV decrease
temperature at RAMP
control
R/W EUS (0 ~ 100%) ℃
EUS
(0%)
162
(A2)
262
(106)
RMIN
Set SV change time
(min.) at RAMP control
R/W 0 ~ 1000 Min. 0