Multi Loop Controller
32
Symbol INP Input type Input scope (oC) Degree
TC
1 K
(Note2)
-200 ~ 1370
±0.3 % of F.S ±1digit
2 K -199.9 ~ 1370.0
3 J -200 ~ 1200
4 J -199.9 ~ 1200.0
5 E -199 ~ 999
6 E -199.0 ~ 999.0
7 T -50 ~ 400
8 T -50.0 ~ 400.0
9 R 0 ~ 1700
10 B (Note1) 0 ~ 1800
11 S - 0 ~ 1700
12 L
(Note2)
-199 ~ 900
13 L -199.0 ~ 900.0
14 N - -199 ~ 1300 ±0.6 % of F.S ±1digit
15 U
(Note2)
-50 ~ 400
±0.3 % of F.S ±1digit
16 U -50.0 ~ 400.0
17 W - 0 ~ 2300
18 PLII - 0 ~ 1300
RTD
20 KPt100
(Note3)
-200 ~ 500
21 KPt100 -199.9 ~ 500.0
22 Pt100 - -200 ~ 640
23 Pt100 - -199.9 ~ 640.0
DCV
30 0 - 10 V d.c. 0 ~ 10000
31 1 - 5 V d.c. 1000 ~ 5000
32 0 - 100 ㎷ d.c. 0 ~ 1000
F.S is from minimum value to maximum value of possible reading range of each input, and digit is
minimum indication value.
(Note 1) 0~400oC range: ±10% of F.S±1digit
(Note 2) Below 0oC: ±1% of F.S±1digit
(Note 3) -150.0 ~ 150.0oC range: ±1% of F.S±1digit
※ When using 4 -20mA direct current input, please select input code 31, and attach 250 Ω of electric resistance
to both input terminals.
3.3. Manipulation and run
3.3.1 Input section
● Input type (INP)
It is a parameter setting input signal (sensor) type, and once this input type is set, input scope (range) and
decimal point indication or not is determined depending on the type of input. Input type can be set differently by
channel. All parameters related to PV are initialized when changing input type.
※ Set value (SV), Event Set value (EVVL), Event Hysteresis(EVHY), Event Loop break Dead Band (LBD), Set
value High/Low Limit (SVH/SVL), Reading High/Low Limit (FRH/FRL), Scale High/Low Limit Setting (SLH/SLL),
Set value Increase Temperature (RTUP), Set value decrease temperature(RTDN), input correction (BS), ON/OFF
control hysteresis (HYS),decimal point(DOT),proportional band(PB), integral time (TI), differential time (TD) 2 DOF
ALPHA value (AP) set value(SV),event set value(EVVL),event hysteresis (EVHY), event loop break alarm dead
band (LBD)