EasyManua.ls Logo

HANYOUNG NUX ML-D Series - ML-D4 Register Description

HANYOUNG NUX ML-D Series
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
Before staring Installation Operation Specifications
No.
0
Description
+100 +200 +300 +400
Description by channel
93 - -
- - - -
-
94 - -
- - - -
-
95 ADDR Switch address - - - - -
96 MAX_CH Number of channels - - - - -
97 R_SYS System data - - - - -
98
R_OPT Option data - - - - -
99 ROMVER Version - - - - -
3.2.4 ML-D4register description
Register address (HEX) Description
40001(0) ~ 40099(63)
CH1~4 PV, SV, MV, TSV, CHSTS, EVSTS and common channel setting
※ Please use address
40000 for Modbus
communication
40101(65) ~ 40199(C7) CH1 related setting
40201(C9) ~ 40299(12B) CH2 related setting
40301(12D) ~ 40399(18F) CH3 related setting
40401(191) ~ 40499(1F3) CH4 related setting
Register address (HEX) Symbol
Description
Property
(R/W)
Setting range Unit
Initial
value
CH1 CH2 CH3 CH4
n : Number
of channel
1(1) 2(2) 3(3) 4(4) PV
Process value
R EU(0 ~ 100%) -
6(6) 7(7) 8(8) 9(9) SV
Set value
R/W EU (0 ~ 100%) EU (0%)
11(B) 12(C) 13(D) 14(E) MV
Manipulated
Value
R 0.0 ~ 100.0 % -
16(10) 17(11) 18(12) 19(13) CHSTS
Channel
status
R
OR run for situation occurrence
15 Bit: Set “1” at System Data error
14 Bit: Set “1” at Calibration Data error
13 Bit: Set “1” at input circuit error
12 Bit: Set “1” at EEPROM error
11 Bit: Set “1” after 24 hours of auto toning (AT)
10 Bit: Set “1” at standard contact point
correction (RCJ) error
9 Bit: Set “1” when exceeding ±5% input range
8 Bit: Set “1” at input sensor error (B. OUT)
2 Bit: Set “1” at auto tuning (AT) run
1 Bit: Set “1” at monitor mode
0 Bit: Set “1” at run start
ABS -
21(15) 22(16) 23(17) 24(18) TSV
Current target
set value
R EU (0 ~ 100%) EU (0%)
26(1A) EVT_STS
Event status
R
Indication of occurrence to all events
previously set
0: no event occurred
1: event occurred
ABS -
27(1B)
EVBUS_STS
Event bus output
status
R
Event bus output OR run
7 Bit(128): Set “1” at event bus8 output occurrence
6 Bit(64): Set “1” at event bus7 output occurrence
5 Bit(32): Set “1” at event bus6 output occurrence
4 Bit(16): Set “1” at event bus5 output occurrence
3 Bit(8): Set “1” at event bus4 output occurrence
2 Bit(4): Set “1” at event bus3 output occurrence
1 Bit(2): Set “1” at event bus2 output occurrence
0 Bit(1): Set “1” at event bus1 output occurrence
ABS -
31(1F) LOCK
Parameter
setting lock
R/W
0: possible to edit all parameters
1: possible to edit only SV, R/S, AT, CHEN
parameters
2. impossible to edit all parameters
ABS 0
32(20)
COMCHK
Time setting for
RS485
communication
disconnection
detection time
R/W
0: OFF
1 ~ 3,600
second
0 (OFF)
33(21)
PARA_SAVE
Save parameter
when
communication
R/W
0: Automatic parameter save
1: save manually using PARA_COPY
parameter
ABS 0