47
Before staring Installation Operation Specifications
●Execute all parameter save (PARA_COPY)
When parameter is not saved by RS485 communication, with this function, all parameters can be saved
by setting PARA_SAVE to “1”. When parameters such as set value (SV) change frequently, this is used
to increase memory lifespan by saving parameter at desired time after setting PARA_SAVE to “1”, in
order to prevent shortening lifespan of memory, where parameters are saved
Depending on warning occurrence type, process value (PV) and Manipulated Value (MV) are
processed as follows.
3.3.5 Warning occurrence and handling
Type Cause Process value (PV) display Manipulated Value (MV) state
B.OUT Input sensor error
Reverse run: 105%,
forward run: -5%
PO output after closing control
OVER
PV is out of input range
within ±5%
Normal process Normal process
RJC RJC error
Reference junction compensation
temperature is normalized to the deleted
temperature value.
Reference junction compensation
temperature is normalized to the
deleted temperature value.
ATE Auto tuning error Normal process Normal process
EEPROM EEPROM error Reverse control: 105%, control: -5% 0%
ADC Input circuit error Reverse control: 105%, control: -5% 0%
CALIB
Calibration error
Reverse control: 105%, control: -5% 0%
SYSD System Data error Reverse control: 105%, control: -5% 0%