41
Before staring Installation Operation Specifications
● Event type (EVTY)
Event type setting can be performed with event number at EVT parameter.
※ O: have stand by, X: do not have stand by
Event
type
Event type
Stand by
(have/not have)
0 None X
1 Deviation high limit X
2 Deviation low limit
X
3
Deviation high/
low limit
X
4 Within deviation range
X
5 Deviation high limit O
6 Deviation low limit O
7
Deviation high/
low limit
O
8 Within deviation range O
9 PV high limit X
Event
type
Event type
Stand by
(have/not have)
10 PV low limit X
11 PV high limit O
12 PV low limit
O
13 SV high limit X
14 SV low limit X
15
Loop break alarm
(LBA)
X
16 -
-
17
Run
X
18 Stop/monitor (Ready) X
19 Fail X
Run based on event type is as follows.
※ ▲ : Event set value (EV) △: SV
Event
type
Event
run
Deviation
high limit
Deviation
low limit
Deviation
high/low
limit
Within
deviation
range
Event
type
Event
run
PV
high limit
PV
low limit
SV
high limit
SV
low limit
EVT_HYS
Alarm zone
PV
PV
EVT_HYS
Alarm zone
PV
EVT_HYS
Alarm zone
PV
EVT_HYS
Alarm zone
PV
EVT_HYSEVT_HYS
Alarm zone
EVT_HYS
Alarm zone
PV
EVT_HYS
Alarm zone
PV
Alarm zone
PV
Alarm zone
PV
*1: Only for ML-D2H