8-4. Setup Menu (STUP)
Communication Group (G.COMM)
Output Group (G.OUT)
Menu Code Parameter Setting Range
Display
Condition
Default
Value
PWD Password 0 ~ 9999 PWD.C 0
PR-S
RS485, RS422
Protocol select
PC-LINK / PC-LK-S
/ MODBUS ASCII / MODBUS RTU
OPT
PC-LINK
BPS Baud Rate 600 - 38400 9600
PRI Parity NONE / EVEN / ODD NONE
STP Stop Bit 1, 2 1
DLN Data Length 7, 8 (Except PC-LIN : 8) 8
ADR Address 1 ~ 99 1
RP.T Response Time 0 ~ 10 0
Menu
Code
Parameter Setting Range
Display Condition Default Value
PWD
Password 0~9999
PWD.C 0
OUT Output Type Please refer output type Always
Universal : Relay
Heating/Cooling :
SSR/SSR
O.ACT
Output Action
REVERSE
DIRECT
Universal REVERSE
HCT Heat cycle Time 1 ~ 1000 s
RLY or SSR Output
(Except ON/OFF
control)
RLY : 30 s
SSR : 2 s
CCT Cool cycle Time 1 ~ 1000 s
Heating/Cooling RLY
or
SSR output
RLY : 30 s
SSR : 2 S
HYS
〔Hysteresis
(ON / OFF Control)〕
EUS (0 ~ 100 %)
ON/OFF control
EUS (0.5 %)
Heating, Cooling, Normal 0.0 ~ 100.0 % Heating/Cooling 0.5 %
HEO
Heat Emergency output
Preset Out 1, (Heat)
-5.0 ~ 105.0 %
Heating/Cooling : 0.0 ~ 105.0 %
Always
0.0 %
CEO
Preset Out 2
Cool Emergency output
0.0 ~ 105.0 % Heating/Cooling 0.0 %
OL-H Output Limit High
OL-L + 1digit ~ 105. %
Heating/Cooling: 0.0 ~ 105.0 %
PID 100.0 %
OL-L Output Limit Low
-0.5 % ~ OL-H - 1digit
Heating/Cooling: 0.0 ~ 105.0 %
PID
0.0 %
HC : 100.0 %
Caution
After setting Input group, Output group, please setup other groups.