Hearth & Home Technologies • DV3732SBI, DV3732SBIL • 2215-900 • 9/0926
V
1
Minimum** H
1
Maximum
90 Elbow Only** 2 ft. 610 mm
1/2 ft.** 152 mm 2 ft. 610 mm
1-1/2 ft.** 457 mm 3 ft. 914 mm
2-1/2 ft.** 762 mm 5 ft. 1.5 m
3-1/2 ft. 1.1 m 7 ft. 2.1 m
4-1/2 ft. 1.4 m 15 ft. 4.6 m
H
1
MAX. =15 ft. (4.6 m)
V
1
+ H
1
MAX. = 40 ft. (12.2 m)
** See Warning.
Figure 7.4
1. Top Vent - Horizontal Termination
One Elbow
Note: There MUST be a 25% reduction
in total H when using ex vent except
when using the simple up and out
installation (see Figure 7.3).
Fire Risk.
When using SLP-HRC-SS and SLP-HRC-ZC-SS
termination caps on top vented replaces, a one
foot minimum vertical vent section is required
before installing rst elbow.
When using DVP-TB1 termination cap on top
vented replaces, a three foot minimum vertical
vent section is required before installing first
elbow.
WARNING**
Note: Use SLP Series
components only.
H
1
V
1