DVC/DVH Inverter Mini-Split Heat Controller
40
10.3.7 IPM Malfunction or IGBT Over Current Protection Diagnosis and Solution (P0)
Error Code
P0
Malfunction decision
conditions
When the voltage signal that IPM sends to compressor drive
chip is abnormal, the display LED will show “P0” and unit will
turn off.
Possible Causes Wiring error
IPM malfunction
Outdoor Fan Assembly faulty
Compressor Malfunction
Outdoor PCB Faulty
Trouble shooting:
Check if the wiring between main
PCB and compressor connected by
error and if the wires and connectors
are broken?
Correct the connection or replace
the wires and connectors.
Yes
No
IPM continuity check. Check if the
IPM terminal resistance values are
uniform. Refer to page 64.
Replace the IPM board or replace the
main PCB if the IPM board and main
PCB are integrated together.
No
Check if the outdoor fan runs
properly or the outdoor unit
ventilation is good.
Yes
No
please refer to the below remark, check whether the
resistance of the fan motor is normal. If not, replace
the fan motor.
Yes
Check if the compressor resistance
values are uniform .Refer to page 63.
No
Replace the compressor.
Yes
Replace the outdoor main PCB if the
main PCB and IPM are separate.