DVC/DVH Inverter Mini-Split Heat Controller
22
However, no matter what value T4 is, if the unit
runs with T3<38°F(3°C) for more than 120
minutes and T3 remains lower than 29°F(-2°C)
for more than 3 minutes, the unit will enter
defrosting mode whether or not T2 drops more
than 41°F(5°C) or not.
9.4.2 Ending Defrosting Operation:
If any one of the following items is satisfied, the
defrost operation will end and the unit will return
to normal heating mode.
T3 rises to be higher than TCDE1.
T3 remains higher than TCDE2 for 80
seconds.
The unit has run in defrosting mode for
10 minutes.
Indoor units TCDE1 TCDE2
B-DVC/DVH 09, 12 54°F(12°C)
47°F(8°C)
B-DVC/DVH 18, 24
59°F(15°C)
9.4.3 Defrosting Process
DVC/DVH 9K,12K:
Compressor
on
off
on
on
on
off
off
off
4-way valve
Outdoor fan
Indoor fan
Indoor fan breeze(10s)
xx
10s
no longer than 10m
30s
FrequencyF8
10s
Frequency
F2
Where xx= 60seconds.
DVC/DVH 18K, 24K:
Compressor
on
off
on
on
on
off
off
off
4-way valve
Outdoor fan
Indoor fan
Indoor fan breeze(10s)
xx
no longer than 10m
Frequency
F8
30s
10s
10s
Frequency F2
Where xx=60seconds for 18K model
Where xx=90seconds for 24K model
9.5 Evaporator Coil Temp. Protection
When T2>140°F(60°C), the compressor will
turn off, but will restart when T2<119°F(48°C).
When T2>128°F(53°C), the compressor
frequency will decrease to a lower level and
runs at this level for 20seconds to protect the
unit. When the frequency decreases to
Fmax= F2 and T2>128°F(53°C) for 3 minutes,
the compressor will turn off. However, when the
coil temperature lowers to T2<119°F(48°C) or
T2 remains at 119°F(48°C) for 6 minutes, the
frequency will not be limited by the evaporator
coil temperature (T2).
9.6 Auto-Mode
This mode can be selected using the remote
control. The set temperature (Ts ) can be
changed between 63-86°F (17-30°C).
In auto mode, the machine will choose the
mode according to ΔT, where ΔT =T1-Ts :
ΔT=T1-Ts Auto Mode Function:
ΔT>1°
Cooling
-1°<ΔT≤1° Fan-only
ΔT≤-1°
Heating