EasyManua.ls Logo

Heat Controller B-DVC24SD-1 - Inverter Compressor Drive Error Diagnosis (P4)

Heat Controller B-DVC24SD-1
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
47
Heat Controller DVC/DVH Inverter Mini-Split
45
10.3.9 Inverter Compressor Drive Error Diagnosis and Solution (P4)
Error Code
P4
Malfunction decision
conditions
An abnormal inverter compressor drive is detected by a special
detection circuit, including communication signal detection,
voltage detection, and compressor rotation speed signal
detection, etc.
Possible Causes Wiring mistake
IPM Malfunction
Outdoor Fan Assembly Faulty
Compressor Malfunction
Outdoor PCB Faulty
Trouble shooting:
Check if the wiring between main
PCB and compressor connected by
error and if the wires and connectors
are broken?
Correct the connection or replace
the wires and connectors.
Yes
No
IPM continuity check. Check if the
IPM terminal resistance values are
uniform. Refer to page 64.
Replace the IPM board or replace the
main PCB if the IPM board and main
PCB are integrated together.
No
Check if the outdoor fan runs
properly or the outdoor unit
ventilation is good.
Yes
No
For MSV1-09HRFN1-MT0W and MSV1-12HRFN1- MT0W
models, r
efer to the solution of fan speed has been out
of control malfunction . Find out the cause and have it
solved. For other models, please refer to the below
remark, check whether the resistance of the fan motor
is normal. If not, replace the fan motor.
Yes
Check if the compressor resistance
values are uniform .Refer to page 63.
No
Replace the compressor.
Yes
Replace the outdoor main PCB if the
main PCB and IPM are separate.
Checkwhethertheresistance
of the fan motor is normal.
Ifnot,replacethefanmotor.
Refer to pages 34-35.
Check if the compressor resistance
values are uniform.
Refertothefollowingpage.
Check if the outdoor fan runs
properly and if the outdoor
unit’s ventilation is good.
IPM continuity check. Check if the IPM
terminal resistance values are uniform.
Refer to pages 40-41.
Checkifthewiringbetweenmain
PCB and compressor are properly
connectedandifanywiresor
connectorsarebroken?

Related product manuals