HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
40
Heat Controller, Inc. Water-Source Heating and Cooling Systems
Unit Operating Conditions
Table 15: R-22 HSS Typical Unit Operating Pressures and Temperatures
Table 14d: Size 060 HTS Two-Stage R-410A Typical Unit Operating Pressures and Temperatures
Entering
Water
Temp °F
Water
Flow
GPM/
ton
Full Load Cooling - without HWG active Full Load Heating - without HWG active
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Super-
heat
Sub-
cooling
Water Temp
Rise °F
Air Temp
Drop °F
DB
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Super-
heat
Sub-
cooling
Water Temp
Drop °F
Air Temp
Rise °F
DB
30
1.5
2.25
3
117-127
116-126
115-125
160-180
133-153
125-145
16-21
17-22
18-23
8-13
6-11
5-10
17.5-19.5
11.9-13.9
6.3-8.3
16-22
16-22
16-22
66-76
69-79
72-82
282-302
285-305
289-309
9-15
9-15
9-15
8-13
8-13
9-14
8-10
6-8
4-6
21-27
21-27
22-28
50
1.5
2.25
3
126-136
124-134
123-133
228-248
212-232
195-215
8-13
11-16
14-19
8-13
6-11
5-10
19.8-21.8
14.2-16.2
8.5-10.5
20-26
20-26
20-26
95-105
100-110
105-115
318-338
321-341
324-344
9-15
9-15
9-15
12-17
12-17
12-17
11.3-13.3
8.5-10.5
5.7-7.7
27-33
28-34
30-36
70
1.5
2.25
3
130-140
129-139
128-138
305-325
286-306
266-286
8-13
9-14
11-16
10-15
9-14
7-12
20.3-22.3
14.8-16.8
9.3-11.3
21-27
21-27
21-27
128-138
133-143
139-149
360-380
364-384
368-388
8-14
8-14
8-14
12-17
12-17
12-17
14-16
10.6-12.6
7.3-9.3
33-38
34-40
35-41
90
1.5
2.25
3
133-143
132-142
132-142
398-418
376-396
354-374
8-13
8-13
8-13
10-15
9-14
7-12
19.4-21.4
14.1-16.1
8.8-10.8
20-26
20-26
20-26
173-183
177-187
182-192
407-427
411-431
415-435
8-14
8-14
8-14
13-18
13-18
14-19
18.2-20.2
13.9-15.9
9.6-11.6
42-50
43-51
44-52
110
1.5
2.25
3
138-148
137-147
136-146
505-525
483-503
459-479
6-11
6-11
6-11
10-15
9-14
8-13
18.3-20.3
13.3-15.3
8.3-10.3
19-25
19-25
19-25
Operation Not Recommended
Entering
Water
Temp °F
Water
Flow
GPM/
ton
Full Load Cooling - without HWG active Full Load Heating - without HWG active
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Super-
heat
Sub-
cooling
****
Water Temp
Rise *** °F
Air Temp
Drop °F
DB
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Super-
heat
Sub-
cooling
****
Water Temp
Drop *** °F
Air Temp
Rise °F
DB
30
1.5
2.3
3
61-70
62-71
62-71
100-117
92-109
88-104
12-18
12-18
12-18
12-22
12-22
12-22
21-24
13-16
6-11
21-26
21-26
21-26
34-39
37-42
38-44
163-183
165-185
167-186
5-10
5-10
5-10
5-9
5-9
5-9
7.6-8.4
4.8-5.6
3.4-4.2
14-20
16-22
16-22
50
1.5
2.3
3
79-85
75-83
72-82
145-170
130-155
125-150
10-15
10-15
10-15
9-16
9-16
9-16
20-23
12-15
8-12
20-25
20-25
20-25
51-58
53-62
55-65
175-202
178-206
180-208
9-12
9-12
9-12
8-12
8-12
8-12
10.8-11.9
6.7-8.1
5.1-5.9
23-29
24-30
25-31
70
1.5
2.3
3
78-88
78-90
78-91
180-200
169-187
160-180
8-12
8-12
8-12
7-12
7-12
7-12
19-22
11-14
7-12
19-24
19-24
19-24
71-82
77-89
81-92
215-250
203-235
200-235
10-14
10-14
10-14
6-10
6-10
6-10
14.0-15.2
9.0-10.2
6.7-7.9
28-34
30-37
31-38
90
1.5
2.3
3
79-82
80-93
80-93
230-272
215-248
208-240
8-10
8-10
8-10
7-11
7-11
7-11
18-21
10-14
6-11
17-23
17-23
17-23
Operation Not Recommended
* Based on Nominal 400 CFM per ton per circuit ariflow and 70°F EAT heating and 80/67°F cooling.
** Cooling air and water numbers can vary greatly with changes in humidity.
*** Water temperature difference based upon 1.5 - 3 GPM per ton of active circuit water flow.
**** Using liquid line pressure.