SMA24SA-1 SMH24SA-1
Ph-V-Hz 1, 208/230V~, 60Hz 1, 208/230V~, 60Hz
Capacity Btu/h 24000 24000
Input W 2000 2000
Rated current A 8.8 8.8
SEER Btu/w.h 13 13
Capacity Btu/h —— 24000
Input W —— 2000
Rated current A —— 8.8
HSPF W/W —— 7.7
A 14 14
A 34.8 A 34.8 A
Model PA200X2CS-3MUU PA200X2CS-3MUU
Type ROTARY ROTARY
Brand TOSHIBA TOSHIBA
Capacity Btu/h 19820/20130 19820/20130
Input W 2000/1980W 2000/1980W
Rated current(RLA) A 9.70/8.75A 9.70/8.75A
Locked rotor Amp(LRA) A 34.8 A 34.8 A
Thermal protector UP3SE0396-T39 UP3SE0396-T39
Capacitor uF 50 50
Refrigerant oil ml 750 750
Model YDK50-4B YDK50-4B
Brand WELLING WELLING
Input W 82/69/58 82/69/58
Capacitor uF 3 3
Speed(hi/mi/lo) r/min 1260/1100/990 1260/1100/990
CFM 680/600/550 680/600/550
dB(A) 47/44/42 47/44/42
Model YDK100-6EB YDK100-6EB
Brand WELLING WELLING
Input W 160 160
Capacitor uF 4 4
Speed r/min 740 740
CFM 1475 1475
dB(A) 59 59
oz 84.7 86.4
PSIG 650 650
Liquid si
de/ Gas side in
Ф
3/8/
Ф5/8 Ф
3/8/
Ф5/8
Max. refrigerant pipe length ft 33 33
Max. difference in level ft 16 16
ºF 63-86 63-86
ºF 65-113 19-113
ft
2
430-605 430-605
Model
Power supply
Cooling
Heating
Max. current
Starting current
Compressor
Indoor
fan motor
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Outdoor
fan motor
Outdoor air flow
Operation temp
Ambient temp
Application area
Outdoor noise level
Refrigerant type R410A
Design pressure
Refrigerant
piping
Note:
The noise date is base on semi-anechoic chamber, during actual operation; these values are
normally somewhat different than actual operating condition.
The above design and specifications are subject to change without prior notice.
Heat Controller, Inc. Jackson, MI 49203
- 13 -