CONTROL OVERVIEW
PART 9: CONTROL OVERVIEW (CONTINUED)
Function 10 CH Post Pump Time
CH POST PUMP TIME 10
0 MINUTES
Description: Allow the user to set the central heating pump post purge time once the thermostat is
satisfied: Factory Default: 0 minutes – Range (0 – 10 minutes) .
Function 11
DHW Priority
DHW PRIORITY 11
30 MINUTES
Description: Allows the user to set DHW priority time which is the amount of the time to shut down
the hydronic heating module when the total system control senses a large domestic hot water
usage. Factory Default 30 Minutes – Range ( 0 – 60 Minutes)
Function 12
Error Outdoor Sensor
ERROR OUTD SENSOR 12
ON
Description: Allows the user to set the control to display and error message if an outdoor sensor is
open or shorted – Note: This error does not stop the appliance from running. Factory Default ON /
Selection (ON /OFF/ PHOEN ON)
Function 13
Error System Senor
ERROR SYSTEM SENS 13
ON
Description: Allows the user to set the control to display and error message if the system sensor is
open or shorted – Note: This error does not stop the appliance from running. Factory Default
ON/Selection (ON /OFF).
NOTE: Press the ENTER key to store system parameters.
Function 14
Service Schedule
SERVICE SCHEDULE 14
OFF
Description: Allows the user to select a service date or time based on the boiler run hours to pro-
gram the boiler maintenance schedule. Factory Default OFF / Selection (Date or Run Hours) NOTE:
Without setting this function, Functions 33/34/35/36 will not display.
Function 15
Year
SERVICE SCHEDULE 15
YEAR 00/00/2000
Description: This parameter sets the year of the next service reminder
Hours: