EasyManua.ls Logo

Heatilator CNXT70IT - Vent Diagrams

Heatilator CNXT70IT
55 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12 Heatilator • CNXT Series • 4000-011 Rev N • 11/05
Fire Risk
Explosion Risk
Do NOT pack insulation or other combustibles between fi restops.
ALWAYS maintain specifi ed clearances around venting and fi restop systems.
Install fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.
WARNING
The fi rst 90° elbow MUST be a starter elbow.
To replace the fi rst starter elbow with two 45° elbows, refer to Figure 5.4. All other 90° elbows can be replaced with two 45°
elbows.
General Rules:
SUBTRACT 3 ft (914 mm) from the total H measurement for each 90° elbow installed horizontally.
SUBTRACT 1-1/2 ft (457 mm) from the total H measurement for each 45° elbow installed horizontally.
A maximum of three 90° elbows (or six 45° elbows) may be used in any vent confi guration. Some elbows may be installed
horizontally. See Figure 5.6.
Elbows may be placed back to back anywhere in the system as long as the fi rst 90° elbow is a starter elbow except as
shown in Figure 5.4.
When penetrating a combustible wall, a wall shield fi restop must be installed.
When penetrating a combustible ceiling, a ceiling fi restop must be installed.
H
1
V
1
Figure 5.3 Top Vent-Horiztonal Termination-One Elbow
Table 5.1
V
1
min. V
1
max. H
1
max.
0* - 24 in./610mm
6 in./152 mm - 6 ft/1.83 m
12 in./305 mm - 11 ft/3.35 m
18 in./457 mm - 18 ft/5.49 m
24 in./610 mm - 25 ft/7.62 m
- 25 ft/7.62 m 25 ft/7.62 m
* You may install the elbow directly on top of the
appliance
D. Vent Diagrams
Top Vent—Horizontal Termination—One Elbow

Table of Contents

Related product manuals