EasyManua.ls Logo

HEIL F8MVL - Cooling and Dehumidification Modes; Cooling and Dehumidification Operation

HEIL F8MVL
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48
441 01 2121 01
and continues to hold the gas valve GVM open. If
the burner flame is not proved within two seconds,
the control CPU will close the gas valve GVM, and
the control CPU will repeat the ignition sequence for
up to three more TrialsForIgnition before going to
IgnitionLockout. Lockout will be reset automatically
after three hours, or by momentarily interrupting 115
vac power to the furnace, or by interrupting 24 vac
power at SEC1 or SEC2 to the furnace control CPU
(not at W/W1, G, R, etc.). If flame is proved when
flame should not be present, the furnace control
CPU will lock out of GasHeating mode and oper-
ate the inducer motor IDM on high speed until flame
is no longer proved.
e. BlowerOn delay If the burner flame is proven
the blowerON delays for lowheat and highheat
are as follows:
Lowheat 45 seconds after the gas valve GVM
is opened the blower motor BLWM is turned ON at
lowheat airflow.
Highheat 25 seconds after the gas valve GVM
is opened the BLWM is turned ON at highheat
airflow. Simultaneously, the humidifier terminal HUM
and electronic air cleaner terminal EAC1 are ener-
gized and remain energized throughout the heating
cycle.
f. Switching from Low to HighHeat If the fur-
nace control CPU switches from lowheat to high
heat, the furnace control CPU will switch the in-
ducer motor IDM speed from low to high. The
highheat pressure switch relay HPSR is deener-
gized to close the NC contact. When sufficient pres-
sure is available the highheat pressure switch
HPS closes, and the highheat gas valve solenoid
GVHI is energized. The blower motor BLWM will
transition to highheat airflow five seconds after the
furnace control CPU switches from lowheat to
highheat.
g. Switching from High to LowHeat
The furnace
control CPU will not switch from highheat to low
heat while the thermostat RtoW circuit is closed
when using a singlestage thermostat.
h. BlowerOff Delay When the thermostat is satis-
fied, the R to W circuit is opened, deenergizing the
gas valve GVM, stopping gas flow to the burners,
and deenergizing the humidifier terminal HUM.
The inducer motor IDM will remain energized for a
5second postpurge period. The blower motor
BLWM and air cleaner terminal EAC1 will remain
energized at lowheat airflow or transition to low
heat airflow for 90, 120, 150, or 180 seconds (de-
pending on selection at blowerOFF delay
switches). The furnace control CPU is factoryset
for a 120second blowerOFF delay.
2. TwoStage Thermostat and TwoStage Heating
See Figure 27Figure 33 for thermostat connections.
NOTE: In this mode the lowheat only switch SW12 must
be ON to select the lowheat only operation mode in
response to closing the thermostat RtoW1 circuit. Closing
the thermostat Rto W1andW2 circuits always causes
highheat operation, regardless of the setting of the lowheat
only switch.
The wall thermostat “calls for heat”, closing the RtoW1
circuit for lowheat or closing the R
toW1andW2 circuits
for highheat. The furnace control performs a selfcheck,
verifies the lowheat and highheat pressure switch contacts
LPS and HPS are open, and starts the inducer motor IDM in
highspeed.
The start up and shut down functions and delays described in
item 1. above apply to the 2stage heating mode as well,
except for switching from low to highHeat and vice versa.
a. Switching from Low to HighHeat If the ther-
mostat RtoW1 circuit is closed and the RtoW2
circuit closes, the furnace control CPU will switch
the inducer motor IDM speed from low to high. The
highheat pressure switch relay HPSR is deener-
gized to close the NC contact. When sufficient pres-
sure is available the highheat pressure switch
HPS closes, and the highheat gas valve solenoid
GVHI is energized. The blower motor BLWM will
transition to highheat airflow five seconds after the
RtoW2 circuit closes.
b. Switching from High to LowHeat If the ther-
mostat Rto W2 circuit opens, and the RtoW1
circuit remains closed, the furnace control CPU will
switch the inducer motor IDM speed from high to
low. The highheat pressure switch relay HPSR is
energized to open the NC contact and deenergize
the highheat gas valve solenoid GV
HI. When the
inducer motor IDM reduces pressure sufficiently, the
highheat pressure switch HPS will open. The gas
valve solenoid GVM will remain energized as long
as the lowheat pressure switch LPS remains
closed. The blower motor BLWM will transition to
lowheat airflow five seconds after the RtoW2
circuit opens.
3. Cooling mode
The thermostat “calls for cooling”.
a. SingleSpeed Cooling
See Figure 27 for thermostat connections
The thermostat closes the RtoGandY circuits.
The Rto Y circuit starts the outdoor unit, and the
RtoGandY/Y2 circuits start the furnace blower
motor BLWM on cooling airflow. Cooling airflow is
based on the A/C selection shown in Figure 55. The
electronic air cleaner terminal EAC1 is energized
with 115 vac when the blower motor BLWM is oper-
ating.
When the thermostat is satisfied, the Rto
GandY circuits are opened. The outdoor unit will
stop, and the furnace blower motor BLWM will con-
tinue operating at cooling airflow for an additional
90 seconds. Jumper Y/Y2 to DHUM to reduce the
cooling offdelay to 5 seconds. (See Figure 26)
b. TwoStage Thermostat and TwoSpeed Cooling
See Figure 28 for thermostat connections
The thermostat closes the RtoGandY1 circuits for
lowcooling or closes the RtoGandY1andY2 circuits
for highcooling. The R
toY1 circuit starts the outdoor unit
on lowcooling speed, and the RtoGandY1 circuit starts
the furnace blower motor BLWM at lowcooling airflow which
is the CF (continuous fan) selection as shown in Figure 53.
The RtoY1andY2 circuits start the outdoor unit on
highcooling speed, and the Rto GandY/Y2 circuits start
the furnace blower motor BLWM at highcooling airflow.
Highcooling airflow is based on the A/C (air conditioning)
selection shown in Figure 55.
The electronic air cleaner terminal EAC1 is energized with
115 vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the RtoGandY1 or
Rto GandY1andY2 circuits are opened. The outdoor
unit stops, and the furnace blower BLWM and electronic air
cleaner terminal EAC1 will remain energized for an
additional 90 seconds. Jumper Y1 to DHUM to reduce the
cooling offdelay to 5 seconds. (See Figure 26)
4. Dehumidfy Mode
See Figure 27Figure 33 for thermostat connections.
The H output on the humidify sensing thermostat
should be connected to the furnace control thermostat
terminal DHUM. When there is a dehumidify demand,
the DHUM input is activated, which means 24 vac sig-
nal is removed from the DHUM input terminal. In other
words, the DHUM input logic is reversed. The DHUM

Related product manuals