EasyManua.ls Logo

HEIL F8MVL - Venting

HEIL F8MVL
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
441 01 2121 01
13. Reinstall cover to JBox. Do not pinch wires between
cover and bracket.
Figure 24 FieldSupplied Electrical Box on Furnace
Casing
Power Cord Installation in Furnace JBox
NOTE: Power cords must be able to handle the electrical
requirements listed in Table 6. Refer to power cord
manufacturer’s listings.
1. Remove cover from JBox.
2. Route listed power cord through 7/8in. (22 mm) dia-
meter hole in JBox.
3. Secure power cord to JBox bracket with a strain relief
bushing or a connector approved for the type of cord
used.
4. Secure field ground wire to green ground screw on
JBox bracket.
5. Connect line voltage leads as shown in Figure 25.
6. Reinstall cover to JBox. Do not pinch wires between
cover and bracket.
BX Cable Installation in Furnace JBox
1. Remove cover from JBox.
2. Route BX cable into 7/8in. (22 mm) diameter hole in
JBox.
3. Secure BX cable to JBox bracket with connectors ap-
proved for the type of cable used.
4. Secure field ground wire to green ground screw on
JBox bracket.
5. Connect line voltage leads as shown in Figure 25.
6. Reinstall cover to JBox. Do not pinch wires between
cover and bracket.
24V Wiring
Make field 24v connections at the 24v terminal strip. (See
Figure 25 Figure 33) Connect terminal Y/Y2 as shown in
Figure 27Figure 33 for proper cooling operation. Use only
AWG No. 18, colorcoded, copper thermostat wire.
The 24v circuit contains an automotivetype, 3amp. fuse
located on the control. Any direct shorts during installation,
service, or maintenance could cause this fuse to blow. If fuse
replacement is required, use ONLY a 3amp. fuse of identical
size.
ACCESSORIES
1. Electronic Air Cleaner (EAC)
Connect an accessory Electronic Air Cleaner (if used)
using 1/4in female quick connect terminals to the two
male 1/4in quickconnect terminals on the control
board marked EAC1 and EAC2. The terminals are
rated for 115VAC, 1.0 amps maximum and are ener-
gized during blower motor operation. (See Figure 26)
2. Humidifier (HUM)
Connect an accessory 24 VAC, 0.5 amp. maximum hu-
midifier (if used) to the 1/4in male quickconnect HUM
terminal and COM24V screw terminal on the control
board thermostat strip. The HUM terminal is energized
when blower is energized in heating. (See Figure 26)
NOTE: DO NOT connect furnace control HUM terminal to H
terminal on humidity sensing thermostat, or similar device.
See the humidity sensing thermostat, instructions for proper
connection.
VENTING
The furnace shall be connected to a listed factory built
chimney or vent, or a claytile lined masonry or concrete
chimney. Venting into an unlined masonry chimney or
concrete chimney is prohibited.
When an existing Category I furnace is removed or replaced,
the original venting system, may no longer be sized to
properly vent the attached appliances. An improperly sized
Category I venting system could cause the formation of
condensate in the furnace and vent, leakage of condensate
and combustion products, and spillage of combustion
products into the living space.

Related product manuals