47
441 01 2121 01
The wall thermostat “calls for heat”, closing the RtoW
circuit. The furnace control performs a selfcheck, verifies the
lowheat and highheat pressure switch contacts LPS and
HPS are open, and starts the inducer motor IDM in
highspeed.
a. Inducer Prepurge Period
(1.) If the furnace control CPU selects lowheat
operation the inducer motor IDM comes up to
speed, the lowheat pressure switch LPS
closes, and the furnace control CPU begins a
15second prepurge period. If the lowheat
pressure switch LPS fails to remain closed the
inducer motor IDM will remain running at high
speed. After the lowheat pressure switch re
closes the furnace control CPU will begin a
15second prepurge period, and continue to
run the inducer motor IDM at highspeed.
(2.) If the furnace control CPU selects highheat
operation, the inducer motor IDM remains run-
ning at highspeed, and the highheat pres-
sure switch relay HPSR is deenergized to
close the NC contact. When sufficient pressure
is available the highheat pressure switch HPS
closes, and the highheat gas valve solenoid
GVHI is energized. The furnace control CPU
begins a 15second prepurge period after the
lowheat pressure switch LPS closes. If the
highheat pressure switch HPS fails to close
and the lowheat pressure switch LPS closes,
the furnace will operate at lowheat gas flow
rate until the highheat pressure switch closes
for a maximum of 2 minutes after ignition.
Figure 55 Cooling (A/C) or ContinuousFan (CF) Airflow Selection Chart
SWITCH SW2 or SW3 POSITIONS
SWITCH SW2 or SW3 POSITIONS
b. Igniter WarmUp At the end of the prepurge peri-
od, the HotSurface Igniter HSI is energized for a
17second igniter warmup period.
c. TrialForIgnition Sequence When the igniter
warmup period is completed the main gas valve
relay contact GVR closes to energize the gas valve
solenoid GVM. The gas valve solenoid GVM per-
mits gas flow to the burners where it is ignited by
the HSI. Five seconds after the GVR closes, a
2second flame proving period begins. The HSI
igniter will remain energized until the flame is
sensed or until the 2second flame proving period
begins. If the furnace control CPU selects high
heat operation, the highheat gas valve solenoid
GVHI is also energized.
d. FlameProving When the burner flame is proved
at the flameproving sensor electrode FSE, the in-
ducer motor IDM switches to lowspeed unless the
furnace is operating in highheat, and the furnace
control CPU begins the blowerON delay period