HI 800 101 HIMatrix Engineering Manual
4.3 Short-Circuit Characteristics of the Output Channels
In the event of a short-circuit in one output channel the HIMatrix automation devices switch
off the affected channel. In the event of multiple short-circuits the channels are switched off
individually in accordance to their power consumption.
If the maximally permitted current for all outputs is exceeded, all outputs are shut down and
cyclically reconnected.
The terminals for output circuits may not be plugged with
load connected. With existing short-circuits the resulting
high current may damage the terminals.