4 Start-up X-DI 64 51
Page 36 of 50 HI 801 177 E 4.00
4.3.4 Submodule Status [DWORD]
Coding of the variable Submodule Status.
Coding Description
0x00000001 Hardware unit fault (submodule).
0x00000002 Reset of an I/O bus
0x00000004 Faults detected while configuring the hardware
0x00000008 Fault detected while verifying the coefficients
0x00000010 First temperature threshold exceeded (warning temperature)
0x00000020 Second temperature threshold exceeded (limit temperature)
0x00000040 Overcurrent, module shutdown
0x00000080 Reset on the chip select monitoring
0x00800000 Module fault reference voltage A
0x01000000 Fault reference voltage A (overvoltage)
0x02000000 Fault reference voltage B (undervoltage)
0x04000000 Module fault reference voltage B
0x08000000 Fault auxiliary voltage
0x10000000 Fault reference voltage A (undervoltage)
0x20000000 Fault reference voltage B (overvoltage)
0x40000000 Fault chip select monitoring A
0x80000000 Fault chip select monitoring B
Table 20: Submodule Status [DWORD]