(APPENDIX IV) DIMENSIONS, WIRING AND MECHANICAL PARTS | PAGE 55
Signal Description Type Characteristics
Voltage free relay outputs
CRC C network breaker Output Voltage free relay output
CRNC NC network breaker Output Voltage free relay output
CRNA NA network breaker Output Voltage free relay output
CGC C genset breaker Output Voltage free relay output
CGNC NC genset breaker Output Voltage free relay output
CGNA NA genset breaker Output Voltage free relay output
SCC Circuit breaker C Output Voltage free relay output
SCNC Circuit breaker NC Output Voltage free relay output
SCNA Circuit breaker NA Output Voltage free relay output
BTC Fuel transfer pump C Output Voltage free relay output
BTNA Fuel transfer pump NA Output Voltage free relay output
The USB connector complies with the standard 2.0.
To power the control unit, it is recommended that a cable be used with a
cross-section of 1 mm
2
.
The equipment must be isolated or disconnected before connecting the voltage
input for the generator, as there is a risk of damage.
A cable with a cross-section of 2.5 mm
2
must be used for +BAT, ARR, PR and PC
connections. For the rest of the connections it is recommended that a cable be
used with a cross-section of 1 mm
2
.
The control unit must be mounted at the front of an electrical panel, if possible in
the centre to allow easy wiring.
There are no special ventilation requirements due to the low power consumed by
the control unit.
The surface areas of the equipment and the external face should be cleaned with
a damp cloth.
The equipment is included within the measurement category CAT III 600 V for
measurements performed in the building installation.
Disconnection means should be incorporated to the xed installation in accord-
ance with installation regulations. Such means must have contact separation for
all poles that provide full disconnection in category III overvoltage conditions.
INPUTS AND OUTPUTS
Signal Description Type Characteristics
Power supply
8÷36V Positive power supply Power supply Module supply voltage from 8 to 36 V
-BAT Negative power supply Power supply Module supply negative
MAN Manual Input Start up PNP digital input
CAN Bus
CANS CAN bus screen CAN Bus CAN communication
CANL L signal of CAN bus CAN Bus CAN communication
CANH H signal of CAN bus CAN Bus CAN communication
Digital inputs
PEM Emergency Stop Input NPN digital input
ENT1 Auxiliary input 1 Input NPN digital input
ENT2 Auxiliary input 2 Input NPN digital input
ENT3 Auxiliary input 3 Input NPN digital input
Genset three-phase current inputs
IL3 T-phase current Input
Analogue input for current measure-
ment
IL2 S-phase current Input
Analogue input for current measure-
ment
IL1 R-phase current Input
Analogue input for current measure-
ment
ILN Neutral current Input
Analogue input for current measure-
ment
Grid three-phase voltage input
VR3 T-phase voltage Input
Analogue input for voltage measure-
ment
VR2 S-phase voltage Input
Analogue input for voltage measure-
ment
VR1 R-phase voltage Input
Analogue input for voltage measure-
ment
VRN Neutral Input
Analogue input for voltage measure-
ment
Genset three-phase voltage input
VG3 T-phase voltage Input
Analogue input for voltage measure-
ment
VG2 S-phase voltage Input
Analogue input for voltage measure-
ment
VG1 R-phase voltage Input
Analogue input for voltage measure-
ment
VGN Neutral Input
Analogue input for voltage measure-
ment