14
Clamp-on sensor CLAMP ON SENSOR 9694 CLAMP ON SENSOR 9660 CLAMP ON SENSOR 9661
Appearance
Primary current rating 5A AC 100A AC 500A AC
Output voltage 10mV/A AC AC 1mV/A AC AC 1mV/A AC
Measurement range See input specications
Amplitude accuracy * ±0.3%rdg.±0.02%f.s. * ±0.3%rdg.±0.02%f.s. * ±0.3%rdg.±0.01%f.s *
Phase accuracy * ±2° or less * ±1° or less * ±0. or less *
Maximum allowable input * 50 A continuous * 130 A continuous * 550 A continuous *
Maximum rated voltage to earth CAT III 300Vrms CAT III 600 Vrms
Frequency characteristics ±1.0% or less for 66Hz to 5kHz (deviation from specified accuracy)
Cord length 3m (9.84ft)
Measurable conductor diameter Max.φ15mm (0.59") Max.φ46mm (1.81")
Dimensions, Mass
46W(1.81")×135H(5.31")×21D(0.83")mm,
230g(8.1oz.)
78W(3.07")×152H(5.98")×42D(1.65")mm,
380g(13.4oz.)
* : 45 to 66Hz
Clamp-on sensors specications (Options)
Clamp-on sensor CLAMP ON SENSOR 9669 CLAMP ON SENSOR 9695-02 CLAMP ON SENSOR 9695-03
Appearance
Note:
CONNECTION CORD 9219 (sold separately) is required.
Primary current rating 1000 A AC 50A AC 100A AC
Output voltage 0.5mV/A AC 10mV/A AC 1mV/A AC
Measurement range See input specications
Amplitude accuracy * ±1.0%rdg.±0.01%f.s. * ±0.3%rdg.±0.02%f.s. * ±0.3%rdg.±0.02%f.s. *
Phase accuracy * ±1° or less * Within ±2° * Wit hin ±1° *
Maximum allowable input * 1000 A continuous * 130 A continuous * 130 A continuous *
Maximum rated voltage to earth CATIII 600Vrms CATIII 300Vrms
Frequency characteristics
Within ±2% at 40Hz to 5kHz (deviation from accuracy)
Within ±2% at 40Hz to 5kHz (deviation from accuracy)
Cord length 3m (9.84ft) CONNECTION CORD 9219 (sold separately) is required.
Measurable conductor diameter
Max. φ55 mm(2.17"), 80 (3.15")×20(0.79") mm busbar
Max. φ15mm(0.59")
Dimensions, Mass
99.5W (3.92") × 188H (7.40") × 42D (1.65") mm
,
590g (20.8 oz.)
51W(2.01")×58H(2.28")×19D(0.75")mm, 50g(1.8oz.)
Options (sold separately) CONNECTION CORD 9219 (Cord length:3m (9.84ft)
* : 45 to 66Hz
CONNECTION CORD 9219
Clamp-on sensor
AC FLEXIBLE CURRENT SENSOR
CT9667-01
AC FLEXIBLE CURRENT SENSOR
CT9667-02
AC FLEXIBLE CURRENT SENSOR
CT9667-03
Appearance
Primary current rating 500A AC, 5000A AC (selectable)
Output voltage 500 mV AC f.s.
Measurement range See input specications
Amplitude accuracy * ±2.0%rdg.±0.3%f.s. *
Phase accuracy * ±1° or less *
Maximum allowable input * 10000 A continuous *
Maximum rated voltage to earth
CATIII 1000 Vrms
CATIV 600 Vrms
Frequency characteristics ±3dB or less for 10 Hz to 20kHz (within ±3dB)
Cord length Sensor to circuit: 2m (6.56ft), Circuit to connector: 1m (3.28ft)
Measurable conductor diameter Max.
φ100mm (3.94”) Max. φ180m m (7. 0 9 ) Max. φ254mm(10.0")
Dimensions, Mass
Circuit box: 35W (1.38") × 120.5H (4.74") × 34D (1.34") mm
Sensor cable diameter: φ7.4 mm (0 . 2 9 ) Sensor cable diameter: φ13 mm (0.51”)
Mass 280g (9.9 oz.) 470 g (16.6 oz.)
Power supply LR6 alkaline battery x2, AC Adapter (option) , or external 5 to 15 V DC power supply
Options (sold separately)
AC ADAPTER 9445-02 (universal 100 to 240VAC , 9V/1A output/for USA)
AC ADAPTER 9445-03 (universal 100 to 240VAC , 9V/1A output/for Europe)
* : 45 to 66Hz
Not CE marked
Insulated
conductor
Not CE marked
Insulated
conductor

Other manuals for Hioki PW3198

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hioki PW3198 and is the answer not in the manual?

Hioki PW3198 Specifications

General IconGeneral
BrandHioki
ModelPW3198
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals