Sensor Calibration
© 2009 Hirschmann Automation and Control GmbH · Branch Office Ettlingen · eMail: info.ecs@hirschmann.de · www.hirschmann.com 16
24 183 69 1012e (Generic) / 2009-02-26 / Rev. 01 / rk.
When the boom angle is within the calibration range, the screen will add the
‘CHANGE ?’ / ‘SET’ and ‘OK’ text as shown below:
▼ Calibration for "40°" angle:
leave the service menu
adjust actual angle
set current angle to defined angle
• Measure the boom angle with the inclinometer and when the boom is positioned in the calibration
range, compare the measured angle to the displayed angle.
• If the indicated angle is within +/- 0.1 degrees of the measured angle, confirm with ‘OK’.
Otherwise, select ‘SET’ to adjust the angle.
▼ Adjust "40°" angle:
leave the service menu
increase angle value by 0.1°
Confirm
decrease angle value by 0.1°
• Once you push ‘SET’ , the screen is going to change to the angle adjustment screen. Use the ‘+’
and ‘-‘ buttons to adjust the indicated angle to match the measured angle.
• When the display shows the correct angle, press ‘OK’.
Press ESC to leave sensor adjustments and return to normal LMI screen.
• Now repeat procedure as shown for the boom angle 65° and 75°.
If values were modified a confirmation screen appears at the end: