Installation RSPE 30/32/35/37
Release
12
10/2015
45
With a non-redundant supply of the supply voltage, the device reports the
loss of a supply voltage. You can prevent this message by applying the
supply voltage via both inputs, or by changing the configuration in the
Management.
2.6.5 Signal contact
Connect the signal contact wires with the connectors of the terminal block.
Fasten the wires connected by tightening the terminal screws.
2.7 Operating the device
Relevant for North America:
The torque for tightening the supply voltage terminal block on the device is
4.5 lb-in (0.51 Nm).
The torque for tightening the terminal block for the signal contact on the
device is 3 lb-in (0.34 Nm).
Proceed as follows:
Use screws to secure the connectors to the device.
Enable the supply voltage.
WARNING
ELECTRIC SHOCK
Before connecting the electrical wires, always verify that the requirements
listed are complied with.
See “Requirements for connecting electrical wires” on page 6.
Ground the device before connecting any other cables.
Failure to follow these instructions can result in death, serious injury,
or equipment damage.