EasyManua.ls Logo

Hirschmann RSPE 32 - Electromagnetic Field and Transient Immunity; Voltage Surge and Conducted Disturbance Immunity

Hirschmann RSPE 32
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58
Installation RSPE 30/32/35/37
Release
12
10/2015
EN 61000-4-2
IEEE C37.90.3
Air discharge ±8kV ±8kV ±8kV ±15kV
Electromagnetic field
EN 61000-4-3 80 MHz ... 3000 MHz 10 V/m 10 V/m 20 V/m 10 V/m
IEEE 1613 80 MHz ... 1000 MHz 35 V/m
Fast transients (burst)
EN 61000-4-4
IEEE C37.90.1
DC supply connection ± 2 kV ± 2 kV ± 2 kV ± 4 kV
EN 61000-4-4
IEEE C37.90.1
Data line ±4kV ±4kV ± 2kV ±4kV
Voltage surges - DC supply connection
EN 61000-4-5 line/ground ± 2 kV ± 2 kV ± 2 kV ± 2 kV
IEEE 1613 line/ground ± 5 kV
EN 61000-4-5 line/line ± 1 kV ± 1 kV ± 1 kV ± 1 kV
Voltage surges - data line
EN 61000-4-5 line/ground ± 1 kV ± 1 kV ± 2 kV ± 2 kV
Conducted disturbances
EN 61000-4-6 150 kHz ... 80 MHz 10 V 10 V 10 V 10 V
EMC interference
immunity
Standard
applications
Navy applications Railway
applications
(trackside)
Substation
applications

Table of Contents

Related product manuals