34
INSTALLATION & MAINTENANCE MANUAL
NOTES:
C8=00 is the factory default setting. If C8 is le unchanged, the system will sense the conditioned
space temperature from only one point (i.e.the sensor in the return air) and not from the individual
zones as intended.
If remote temperature sensors are used, they must be plugged into the Zone Interface Box and not
into the indoor unit.
(2) Indoor Unit ESP Setting
Before operating Indoor Unit auto ESP function, please set all zone ON and
all zones’ airow tap to H tap rst. This can be done using "Turn on All Zones"
in Zone Installation Menu.
NOTES:
Please use auto ESP setting mode or manual ESP setting mode in Indoor Unit ESP setting, and
correctly set the ESP value, otherwise zone airow volume may be inuenced.
Do not operate Indoor Unit auto ESP function when system starting.
7.3 Premium Zoning Kit Notes
(1) Installation related
a. At least one zone must be set enabled.
b. Spill zone and common zone are recommended to be installed in public spaces such as living
room, corridors or stairs space.
c. The damper timing (the time taken for the dampers to move from the fully open to fully closed
position and vice-versa) must be the same for all damper motors.
d. Each zone (except common zone) must be paired with at least one of the following:
One or more room temperature sensors (Indoor Unit Inlet Air Sensor / Primary Wired Remote
Controller Sensor / Secondary Wired Remote Controller Sensor / Remote Sensor 1 / Remote
Sensor 2)
One Thermostat
(2) Function conict
a. To ensure reliable operation of both the air conditioner and zoning kit, please ensure that the
function settings below are remain on the factory default setting of 00.
No. Item Default Setting
1 b9 00
2 C5 00
3 d5 00
4 EE 00
5 EF 00
6 FA 00
7 K6 00
8 P2 00
9 R1 00
b. DSW6-6 of indoor unit PCB is not allowed to be set to ON.