Unit: mm
Service Space
Service Access Door 1 (*)
Electrical Box
( 450)
Service Access Door 3
Min. 300
Upper Side
Bottom Side
Min. A
Min. 100
Min. 500
Min. 100
4-Suspension Bolt
M10 or W3/8
(Field-Supplied)
Service Access Door 2
( 450)
( 450)
100
50
* Service access door 1 is required for models
CH-AP08MSSX, CH-AP12MSSX and CH-AP16MSSX.
100
100
50
8
P5417025-rev.1
4.2 InitialCheck
● InstalltheCH-Boxwithaproperclearance
arounditformaintenanceworkingspace,as
showninFigure4.1below.
Size
Model
A
CH-AP04MSSX
JCH-AP04MSSX
100
CH-AP08MSSX
JCH-AP08MSSX
400
CH-AP12MSSX
JCH-AP12MSSX
CH-AP16MSSX
JCH-AP16MSSX
PurposeofEachServiceAccessDoor
Name Purpose
ServiceAccess
Door1
Useduringinspectionofindoorunit
connectingside.
ServiceAccess
Door2
Useduringinspectionofindoorunit
connectingside.
ServiceAccess
Door3
Useduringinspectionofelectrical
componentsinsideelectricalbox.
Figure4.1ServiceSpace
● Checktoensurethattheceilingissufciently
strongtosustaintheCH-Box.Iftheceilingis
weak,abnormalsoundandvibrationmayoccur.
● Whentheelectronicexpansionvalveinthe
CH-Boxisactivated,achangeinthetypical
refrigerantowsoundsmaybeheardor
perceivedfromtheCH-Box.Takethefollowing
actiontominimizethesound.
(A) InstalltheCH-Boxinsidetheceiling.Asfor
theceilingmaterial,selectamateriallikea
plasterboardatleast9mm(1inch),which
minimizesoperationsound.
(B) DonotinstalltheCH-Boxinaplacenear
bedroomsorhospitalrooms.
● Whentheoperationischangedtocooling/
heatingmode,achangeinthetypicalrefrigerant
owsoundsmaybeheardorperceivedfromthe
CH-Box.
Therefore,installtheCH-Boxintheceilingof
thecorridorsothattherefrigerantowingsound
maynotbeheardintheroom.
● DonotinstalltheCH-Boxinahotor
humidplace,suchasakitchen,toprevent
condensationontheoutersurfaceofthe
CH-Box.
WheninstallingtheCH-Boxinsuchplaces,
applyadditionalinsulation.
● Payattentiontothefollowingpointswhenthe
CH-Boxisinstalledinahospitalorotherfacility
wherethereareelectronicwavesfrommedical
equipment.
(A) DonotinstalltheCH-Boxwherethe
electromagneticwaveisdirectlyradiatedto
theelectricalboxorcommunicationcable.
(B) InstalltheCH-Boxandcomponentsasfar
aspracticableoratleast3m(10ft)fromthe
electromagneticwaveradiator.
(C) Installanoiselterwhenthepowersupply
emitsharmfulnoises.
● Ensuretheinstallationplaceisconvenient
fortherefrigerantpipingorelectricalwiring
connection.
● Donotdrill,ordrivescrewsintothecabinet.
Useonlymountingpointsprovided.
● IncasetheCH-Boxisrequiredtomovefromthe
ceiling,prepareanotherserviceaccessdoor.