Figure 26 Example of a separated rack configuration
Additional guidelines
You can implement extended cabling with a system installed in customer-
supplied racks, so long as the racks are approved by HDS Customer Sales
& Support (CSS) organization as meeting HDS specifications. Customers
should be informed that HDS requires that customer-supplied racks
housing HDS storage systems must have side panels installed on all
exposed sides.
The “High Temperature Mode” option can be implemented on systems that
use extended cabling.
The minimum microcode that must be installed on the to support the SAS
optical cables is V02 (DKCMAIN 80-02-01-00/01) released October 20,
2014.
You are strongly encouraged to keep your storage system microcode level
current to ensure you have the most up-to-date enhancements and fixes.
If your storage systems is using an earlier microcode release, contact your
authorized service provider for assistance with planning, ordering, and
installing a more current microcode release.
Dual controller in a single rack configuration
In a single rack, you can place both controller chassis to reduce the number
of racks occupying floor space and minimize the operating expenses.
The following diagrams illustrate three configuration options:
Site preparation 101