L100 Inverter
Operations
and Monitoring
4–9
Jogging Command
When the terminal [JG] is turned on and the
Run command is issued, the inverter outputs
the programmed jog frequency to the motor.
Use a switch between terminals [JG] and
[P24] to activate the JG frequency.
The frequency for the jogging operation is set
by parameter A38.
Set the value 01(terminal mode) in A02 (Run
command). Since jogging does not use an
acceleration ramp, we recommend setting the jogging frequency in A38 to 5 Hz or less
to prevent tripping.
The type of deceleration used to end a motor jog is selectable by programming function
A39. The options are:
00 Free-run stop (coasting)
01 Deceleration (normal level) and stop
02 Use DC braking and stop
time
[JG]
terminal
[FW, RV]
(Run)
A39
Jog decel type
Motor
speed
A39
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
06 JG Jogging ON Inverter is in Run Mode, output to motor runs at
jog parameter frequency
OFF Inverter is in Stop Mode
Valid for inputs:
C01, C02, C03, C04, C05
Required settings:
A02= 01, A38 > B82, A38 > 0,
A39
Notes:
No jogging operation is performed when the set
value of jogging frequency A38 is smaller than
the start frequency B82, or the
value is 0 Hz.
Be sure to stop the motor when switching the
function [JG] On or Off.
Example:
FW
JG
See I/O specs on page 4–5.