L100 Inverter Specifications
Getting Started
1–4
L100 Inverter Specifications
Model-specific tables for 200V and 400V class inverters
The following three tables are specific to L100 inverters for the 200V and 400V class
model groups. The table on page 16 gives the general specifications that apply to both
voltage class groups. Footnotes for all specifications tables are on the next page.
Item 200V Class Specifications
L100 inverters, 200V models 002NFE
002NFU
004NFE
004NFU
005NFE
007NFE
007NFU
011NFE
Applicable motor size *2 kW 0.2 0.4 0.55 0.75 1.1
HP 1/4 1/2 3/4 1 1 1/2
Rated capacity (240V) kVA *10 0.5 1.0 1.2 1.6 2.0
Rated input voltage 1-phase: 200 to 240V +5%/-10%, 3-phase: 200 to 230V ±10%,
50/60 Hz ±5% (037LFU, 055LFU & 075LFU 3-phase only)
Rated input current (A), (1-ph / 3-ph) 3.1 / 1.8 5.8 / 3.4 6.7 / 3.9 9.0 / 5.2 11.2 / 6.5
Rated output voltage *3 3-phase 200 to 240V (corresponding to input voltage)
Rated output current (A) 1.4 2.6 3.0 4.0 5.0
Braking Dynamic braking,
approx. % torque,
(short time, stopping
from 50 / 60 Hz) *5
100%:
50Hz,
50%:
60 Hz
Capacitive feedback type, dynamic braking unit and braking resistor
optional, individually installed
DC braking Variable operating frequency, time, and braking force
Weight kg / lb 0.8 / 1.9 0.8 / 1.9 1.3 / 2.9 1.3 / 2.9 2.2 / 4.8
Item 200V Class Specifications, continued
L100 inverters, 200V models 015NFE
015NFU
022NFE
022NFU
037LFU
055LFU
075LFU
Applicable motor size *2 kW 1.5 2.2 3.7 5.5 7.5
HP2357.510
Rated capacity (240V) kVA *10 2.9 4.1 6.3 9.6 12.7
Rated input voltage 1-phase: 200 to 240V ±10%, 3-phase: 200 to 230V ±10%,
50/60 Hz ±5% (037LFU, 055LFU & 075LFU 3-phase only)
Rated input current (A), (1-ph / 3-ph) 16.0 / 9.3 22.5 / 13.0 / 20.0 / 30.0 / 40.0
Rated output voltage *3 3-phase 200 to 240V (corresponding to input voltage)
Rated output current (A) 7.1 10.0 15.9 24 32
Braking Dynamic braking,
approx. % torque,
(short time, stopping
from 50 / 60 Hz) *5
100%:
50Hz
50%:
60Hz
40%:
50Hz
20%:
60Hz
20%:
50Hz
20%:
60Hz
Capacitive feedback type, dynamic braking unit and braking resistor
optional, individually installed
DC braking Variable operating frequency, time, and braking force
Weight kg / lb 2.2 / 4.8 2.8 / 6.2 2.8 / 6.2 5.5 / 12.1 5.7 / 12.6