Start-up and Operation: Check to ensure that all the stop valves are fully opened and no obstacle exists at the inlet/outlet sides
before start-up and during the operation.
Maintenance:Periodically check the high pressure side pressure. If the pressure is higher than the maximum allowable pressure,
stop the system and clean the heat exchanger or remove the cause.
Maximum allowable pressure and high pressure cut-out value:
Refrigerant Maximun allowable pressure (MPa) High pressure switch cut-out value (MPa)
R410A 4.15 4.00 ~ 4.10
? NOTE
Thelabel forthevesselunderPED areattachedonthehighpressure
vessel.Thepressurevesselcapacityandvesselcategoryareindicated
onthevessel.
Location of High Pressure Switch
Compressor
? NOTE
Thehighpressureswitchisindicatedontheelectricalwiringdiagramin
theoutdoorunitasPSHconnectedtoprintedcircuitboard(PCB1)inthe
outdoorunit.
Structure of High Pressure Switch
Contact point
Pressure detected
Connected to the electrical wire
! DANGER
• Donotchangethehigh-pressureswitchlocallyorchangethehighpressurecut-outsetvaluelocally.Ifchanged,itwillcauseserious
injuryordeathduetoexplosion.
• Donotattempttoturnservicevalverodbeyonditsstop.
4 TRANSPORTATION AND HANDLING
When hanging the unit, ensure a balance of the unit, check
safety and lift it up smoothly.
Do not remove any packing materials.
Hang the unit under packing condition with two ropes.
For safety reasons ensure that the outdoor unit is lifted smoothly
and does not lean.
Model Unit Gross Weight (kg)
RAS-(2-2.5)HVNP1 48
RAS-3HVNC1 49
RAS-3HVRNS3 49
1
515 mm
180 mm
275 mm
Center of
gravity
5 BEFORE OPERATION
! CAUTION
• Supply electrical power to the system for approximately 12 hours
before start-up or a long shutdown. Do not start the system
immediatelyafterpowersupply,itmaycausea compressor failure
becausethecompressorisnotheatedwell.
• Whenthesystemisstartedafterashutdownlongerthatapproximately
3months,itisrecommended to check thesystembyyourservice
contractor.
• TurnOFFthemainswitchwhenthesystemistobestoppedforalong
periodoftime:IfthemainswitchisnotturnedOFF,electricitywillbe
used,becausetheoilheaterisalwaysenergisedduringcompressor
stopping.
• Makesure thattheoutdoorunitisnot coveredwithsnoworice.If
covered,removeitbyusing hot water (approximately50°C).Ifthe
watertemperatureishigherthat50°C,itwillcausedamagetoplastic
parts.
TRANSPORTATION AND HANDLING