Remote control switch
indication
Unit condition Wrong portions
Inspection points after power source
OFF
The operation lamp
ickers. (1 time/1 sec.)
and the unit number and
alarm code 03 icker.
The unit does not start.
The power source of outdoor unit in
not turned ON.
The connecting wires of operating line
are incorrect or loosened.
1 Connecting order of each terminal
boards.
2 Screw fastening of each terminal
boards.
? NOTE
Recovering method of FUSE for
operating circuit. There is a fuse
(FUSE4 on indoor unit PCB1, EF1
on outdoor unit PCB1) to protect
operating circuit on the PCB, when
the power lines are connected to
operating lines. If fuse is melted,
operating circuit can be recovered
oncebysettingthedipswitchonthe
PCBasshownin
The operation lamp
ickers. (1 time/2 sec.)
The unit does not start.
Remote control cable is broken.
Contact of connectors is not good.
The connection of remote control
cable is incorrect
This is the same as item 1 and 2
Indication of icker
except above
The unit does not start, or start
once and then stops
The connection of thermistor or other
connectors are incorrect. Tripping of
protector exists, or else.
Check by the abnormality mode table
in the Technical Catalogue (Do it by
service people).
The operation lamp
ickers. (1 Time/1s)
Unit number , alarm
code and unit code
icker
The unit does not start.
The connection of the remote
control cable between indoor units is
incorrect.
Check by the abnormality mode table in
the Technical Catalog (Do it by service
people).
Back to after checking
Instructions for the recovery when the fuse of the transmission circuit is blown out:
1 Correct the wiring to the terminal board.
2 Set pin 2 of DSW7 on the indoor units PCB to ON
12 MAIN SAFETY DEVICES
Compressor Protection
High pressure switch:
This switch cuts out the operation of the compressor when the
discharge pressure exceeds the setting.
Fan Motor Protection
When the fan motor current is reached to the setting, motor
output is decreased.
The other way, when the fan motor current becomes lower,
limitation is cancelled.
Model
RAS-2HVNP1
RAS-2.5HVNP1
RAS-3HVNP1E
RAS-3HVRNS3
For Compressor
Pressure Switches -
Automatic Reset, Non-
Adjustable (each one for
each compressor)
High Cur Out MPa 4.15
Cut-In MPa 3.20
Low Cut-Out MPa 0.30
for control Cut-In MPa 0.20
Fuse -
1~ 230V 50Hz
A 40
CCP Timer - Non-Adjustable
Setting Time min. 3
For Condenser Fan Motor
-
Automatic Reset, Non-
Adjustable (each one for
each motor)
Internal Thermostat
For Control Circuit
A 5
Fuse on PCB
MAIN SAFETY DEVICES