d) In case that upper side obstacles exist (serial units) e) In case of front side and either of the sides are open (serial units)
200
300
0 < L ≤ 1/2 H A ≥ 500
1/2 H < L ≤ H A ≥ 1000
≤ 300
f) In case that surrounding wall exist (serial units)
0 < L ≤ 1/2 A ≥ 500
1/2 H < L ≤ H A ≥ 1000
A
L
1000
0 < L ≤ 1/2 H A ≥ 200
1/2 H < L ≤ H A ≥ 350
g) Horizontal (multiple units) h) Vertical (multiple units)
0 < L ≤ 1/2 H A ≥ 100
1/2 H < L ≤ H A ≥ 200
≥ 1000
≥ 400
≥ 2000
≥ 250
400
≥ 250
≥ 250
400
250
≥ 250
Do not stack more than two units in height. - Close gap (*) to avoid recirculating discharge air ow.
Installing location where the unit will be exposed to strong wind
Follow the instructions below to install on the rooftop or a
location without surrounding buildings, where strong wind is
expected against the product.
Choose a location where the outlet or inlet side of the product
will not be exposed to strong wind.
When the outlet is exposed to strong wind:
Direct strong wind may cause lack of air ow and adversely
affect to the operation.
! CAUTION
Excessive strong wind against
theoutdoorunitoutletmaycause
inverse rotation and damage the
fanandmotor.
In case of blowing strong wind to air outlet the wind guard
(optional) is available to avoid strong wind
Wind guard
Wind guard model
Model
Number of
set required
WSP-264 1
? NOTE
• Thewindguardmustbesetatannualcoolingoperation(inDSW2switch3).
• Forambienttemperature≤10ºC,itisrecommendedtosetthewindguardatcoolingoperation.
UNITS INSTALLATION
PMML0398B rev.0 - 11/2015 - P5416651