4. Electrical wiring
99
SMGB0079 rev.0 - 01/2013
4
4.4.2 Wire size
Connection wiring
Recommended minimum sizes for eld provided wires:
Model Power supply
Power source cable size Transmitting cable size
EN60 335-1 EN60 335-1
All Indoor Units 1~ 230V 50HZ 0.75 mm² 0.75 mm²
IVX Premium Series
RAS-2HVNP
1~ 230V 50HZ
2.5 mm²
0.75 mm²
RAS-2.5HVNP
4.0 mm
2
RAS-3HVNPE
RAS-4HVNPE
6.0 mm
2
RAS-5HVNPE
RAS-6HVNPE
RAS-4HNPE
3N~ 400V 50Hz
2.5 mm
2
RAS-5HNPE
RAS-6HNPE
RAS-8HNPE
6.0 mm
2
RAS-10HNPE
RAS-12HNP
IVX Standard Series
RAS-3HVNC
1~ 230V 50HZ
4.0 mm
2
0.75 mm²
RAS-4HVNCE
6.0 mm
2
RAS-5HVNCE
RAS-6HVNCE
RAS-4HNCE
3N~ 400V 50Hz
4.0 mm
2
RAS-5HNCE
RAS-6HNCE
RAS-8HNCE
6.0 mm
2
RAS-10HNCE
RAS-12HNC
N O T E
• Followlocalcodesandregulationswhenselectingeldwires,CircuitbreakersandEarthLeakagebreakers
• Usethewireswhicharenotlighterthantheordinarypolychloroprenesheathedexiblecord(codedesignation
H05RN-F)