10. Servicing
339
SMGB0079 rev.0 - 01/2013
10
10.3.1.8 Removing the High pressure switch and Pressure switch for control
1 Remove the service cover following Removing service cover.
2 Collect the refrigerant from the check joint according to Removing the compressor, in this chapter.
High pressure switch and pressure switch for control
1 Remove the soundproof cover on the compressor.
2 Disconnect the Faston Terminals of High Pressure Switch and Pressure sensor for PD control.
3 Remove the high pressure switch and the pressure switch for control from the brazed part of discharge piping.
N O T E
Theprocedure(2)isnotrequiredwhenremovingthepressuresensorforPDcontrol.However,checktoensure
thattheconnector(CN100)onO.U.PCB1isdisconnected.
Low pressure switch
1 Open the P plate turning counter clockwise approximately 90° following Opening electrical box (P plate).
• Check that the LED201 (red) on Inverter is OFF when the P plate is opened.
D A N G E R
DONOTtouchelectricalcomponentswhiletheLED201(Red)isONtoavoidelectricalshock.Waituntilthe
LEDturnsoff.
2 Disconnect the Faston Terminals of Low Pressure Switch.
3 Remove the low pressure switch from the brazed part of suction piping.
Upper Cover
Discharge Pipe
Brazing
Part
Brazing Part
Low Pressure Switch
(PSL)
Suction Pipe
High Pressure Switch
(PSH)
Pressure Sensor
for PD Control
Electrical Box
Discharge pipe
Electrical Box
Upper cover
High pressure
switch
Pressure sensor
for PD control
Brazing
part
Low pressure
switch
Suction pipe
Brazing part