3. Piping work and refrigerant charge
74
SMGB0079 rev.0 - 01/2013
3.4.2 Refrigerant charge quantity
Although refrigerant has been charged into this unit, additional refrigerant charge is required according to piping length.
1 The additional refrigerant quantity should be determined and charged into the system according to the following pro-
cedure.
2 Record the additional refrigerant quantity in order to facilitate maintenance and servicing activities.
Refrigerant charge before shipment (W0 (kg))
W0 is the outdoor unit refrigerant charge before shipment explained before, and it’s shown in the following table:
IVX Premium series
Model
Refrigerant charge before
shipment
(W
0
(kg))
Additional refrigerant charge
(P)
(g/m)
Maximum additional
charge
(kg)
Chargeless
length
(m)
RAS-2HVNP 1.6 30 1.5 30 (1)
RAS-2.5HVNP 1.6
30 (for 2 indoor units system:
24)
1.2 30 (1)
RAS-3HVNPE 2.3 40 1.2 30
RAS-4HVNPE 4.1 60 3.9 30
RAS-5HVNPE 4.2 60 3.9 30
RAS-6HVNPE 4.2 60 3.9 30
RAS-4HNPE 4.1 60 3.9 30
RAS-5HNPE 4.2 60 3.9 30
RAS-6HNPE 4.2 60 3.9 30
RAS-8HNPE 5.7 (2) 10.3 30
RAS-10HNPE 6.2 (2) 12.1 30
RAS-12HNP 6.7 (2) 12.1 30
IVX Standard series
Model
Refrigerant charge before
shipment
(W
0
(kg))
Additional refrigerant charge
(P)
(g/m)
Maximum additional
charge
(kg)
Chargeless
length
(m)
RAS-3HVNC 1.9 40 1.2 20
RAS-4HVNCE 2.9 40 1.6 30
RAS-5HVNCE 2.9 60 2.7 30
RAS-6HVNCE 2.9 60 2.7 30
RAS-4HNCE 2.9 40 1.6 30
RAS-5HNCE 2.9 60 2.7 30
RAS-6HNCE 2.9 60 2.7 30
RAS-8HNCE 5.7 (2) 10.3 30
RAS-10HNCE 6.2 (2) 12.1 30
RAS-12HNC 6.7 (2) 12.1 30
(1) For 2 indoor units system conguration, the chargeless length is considered to be 0 m.
(2) Calculated multiplying a constant factor.
C A U T I O N
• Whenchargingrefrigerant,measuretheamountprecisely.
• Overloadingorunderloadingofrefrigerantmaycausecompressorproblems.
• Iftheactualpipinglengthislessthan5mconsultyourdealer.