8. Troubleshooting
279
SMGB0079 rev.0 - 01/2013
8
•  ACT circuit of inverter PCB
Internal circuit of ACT part of inverter module
Non-faulty if [9] – [13] are checked and satised.
(Measure with 1 kΩ range of a tester.)
External Appearance and Internal Circuit of 
Transistor Module
  N O T E
DONOTuseadigitaltester.
9  Check items [1] – [8].
10  Touch [+] side of the tester to DIP-IPM DCL2 terminal, 
and [-] side to [P] of ISPM/DIP-IPM (soldered part) to 
measure the resistance. Normal if all three terminals 
have 100 kΩ or greater
11  Contrary to [10], touch [-] side of the tester to DIP-IPM 
DCL2 terminal, and [+] side to [P] of DIP-IPM (solde-
red part) to measure the resistance. Normal if all three 
terminals have 1 kΩ or greater.
12  Touch [+] side of the tester to DIP-IPM DCL2 terminal, 
and [-] side to [N] of DIP-IPM (soldered part) to mea-
sure the resistance. Normal if all three terminals have 
100 kΩ or greater.
13  Contrary  to [12],  touch [-] side  of the  tester  to DIP-
IPM  DCL2  terminal,  and [+]  side  to  [N]  of  DIP-IPM 
(soldered part) to measure the resistance. Normal if 
all three terminals have 10 kΩ or greater. (Resistance 
gradually increases during measurement.)
Contact with specied terminals 
to measure.
Tester
•  Checking Method of Resistance for Inrush Current Prevention (Built-in Thermal Fuse)
(Measure the resistance under 1 kΩ range of a circuit tester.)
  N O T E
DONOTuseadigitaltester.
By placing the 
+
 side of tester to the 
+
 side of DM1 
(soldering portion)  on inverter  PCB and the 
-
 side  of 
tester to DCL1 on inverter PCB, measure the resistance. 
If the resistance is around 500Ω, it is normal. If the resis-
tance is 0Ω or innity Ω, it is abnormal.
DM1 -
DCL1