EasyManua.ls Logo

Hitachi RAS-8.0HNBRMQ1 - Model of Branch Pipe

Hitachi RAS-8.0HNBRMQ1
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
Required Tightening Torque for Flare Nut
Nominal outside diameter
(according to EN 12735-1 and EN 12735-2)
Minimum wall
Thickness
(mm)
Tightening torque
(N·m)
Metric series
(mm)
Imperial series
(mm) (in)
6 0,80 14 -- 18
6,35 1/4 0,80 14 -- 18
7,94 5/16 0,80 33 -- 42
8 0,80 33 -- 42
9,52 3/8 0,80 33 -- 42
10 0,80 33 -- 42
12 0,80 50 -- 62
12,7 1/2 0,80 50 -- 62
15 0,80 63 -- 77
15,88 5/8 0,95 63 -- 77
18 1,00 90 -- 110
19,06 3/4 1,00 90 -- 110
4.2 Model of Branch Pipe
(1) E-102SN
The model of E-102SN branch pipe is used for the model of RAS-3.0~6.5HNBRKQ1 and
RAS-7.0~12HNBRMQ1 outdoor unit.
Unit: mm
Model E-102SN forRAS-3.0~6.5HNBRKQ1 and RAS-7.0~12HNBRMQ1
Gas Pipe
Liquid Pipe