EasyManua.ls Logo

Hitachi RAS-8.0HNBRMQ1 - 8 Safety and Control Device Setting

Hitachi RAS-8.0HNBRMQ1
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44
8. Safety and Control Device Setting
The compressor is protected by the following devices and their combinations:
(1) High Pressure Switch: This switch cuts out the operation of the compressor when the discharge pressure
exceeds the setting.
(2) Crankcase Heater: This band type heater protects against oil foaming during cold starting, as it is energized
while the compressor is stopped.
Model
RAS-3.0~
3.5HNBRKQ1
RAS-4.0~
6.5HNBRKQ1
RAS-7.0~
8.0HNBRMQ1
RAS-10~
12HNBRMQ1
High Pressure Switch
Automatic Reset, Non-Adjustable Automatic Reset, Non-Adjustable
Cut-Out MPa
4.15
-0.05
-0.2
4.15
-0.05
-0.2
4.15
-0.05
-0.2
4.15
-0.05
-0.2
Cut-In MPa
3.2
+0.15
-0.2
3.2
+0.15
-0.2
3.2
+0.15
-0.2
3.2
+0.15
-0.2
Breaker A
32 40 25 40
Crankcase Heater W
24 28 80 80
CCP Timer
Setting Time
Min
Non-Adjustable
3
Non-Adjustable
3
Non-Adjustable
3
Non-Adjustable
3

Other manuals for Hitachi RAS-8.0HNBRMQ1