EasyManua.ls Logo

Hitachi RAS-8.0HNBRMQ1 - Page 37

Hitachi RAS-8.0HNBRMQ1
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
Table 5.1 Electrical Data and Recommended Characteristics
Model Power Supply
Maximum
Running
Ampacity
(A)
Power Supply
Wiring
(Cores×mm
2
)
Transmission
cable
(Cores×mm
2
)
ELB
Rated
Ampacity
(A)
Rated
Sensitive
Ampacity
(mA)
RAS-3.0~3.5HNBRKQ1 220-240V/1Ph/50Hz 21 3×4.0 2×0.75 32 30
RAS-4.0~6.5HNBRKQ1 220-240V/1Ph/50Hz 31 3×6.0 2×0.75 40 30
RAS-7.0~8.0HNBRMQ1 380-415V/3Ph/50Hz 20 5×6.0 2×0.75 25 30
RAS-10~12HNBRMQ1 380-415V/3Ph/50Hz 28 5×6.0 2×0.75 40 30
(1) Connect the power supply wirings to the terminal block TB1 and ground wiring to the terminal in the
electrical control box. The ELB (Earth leakage breaker), FUSE and S (Main switch) must be installed to
each power source of outdoor unit.
(2) Connect the transmission cables between the outdoor unit and indoor units to the terminals 1 and
2 on the terminal block. The transmission cables must be made from the shielded twist pair cabling.
Proper bonding and termination of the cable shield is required as per guidelines. The installation must
be considered per application and local code requirements. Transmission cable shall be a minimum of
0.75mm
2
, 2-Conductor, Stranded Copper.
(3) For the model of RAS-3.0~6.5HNBRKQ1 outdoor units, the magnetic rings in the package of the
outdoor unit should be used on the power supply wire and transmission cable. For the power supply
wire, two magnetic rings should be paralleled and the wire should through them by one cycle. For the
transmission cable between the outdoor unit and indoor units, the cable should be through the magnetic
ring by 3 cycles.
(4) Connect the transmission cables between the indoor unit and wireless controller to the terminals A and
B on the terminal block.
(5) The transmission cable is required to be separated from the power supply wiring.
Keep at least 5cm distance between the transmission cable and the power supply wiring, and also min.
1.5m distance between the transmission cable and power supply wiring for other electrical device. If the
above is not secured, put the power supply wiring into the metal conduit tube to separate from other
wirings.
(6) Do not connect the power supply wiring to the terminals 1 and 2 on the terminal block for transmission
wiring. Otherwise, printed circuit board may be damaged.
(7) Connect the ground wire for the outdoor/indoor units. The ground wiring work under the condition of
100Ω (Max.) ground resistance should be performed by the qualied person.
(8) Tighten screws for the terminal block according to the following table:
Size Tightening Torque
M4 1.0~1.3 N·m
M5 2.0~2.5 N·m
M6 4.0~5.0 N·m
M8 9.0~11.0 N·m
M10 18.0~23.0 N·m
WARNING
!
The ELB (Earth leakage breaker), FUSE and S (Main switch) must be installed to each power source of
outdoor unit and indoor units. If not, it may cause an electrical shock or re.
Perform the electrical work according to the regulations of each region and this installation and maintenance
manual. A separate, dedicated electrical circuit must be used. If the electrical wiring work is performed
incorrectly or there is a capacity shortage of the power circuit, it will cause an electric shock or re.
Check that the ground wire is securely connected. Otherwise, it may lead to an electrical shock. Do not
connect the ground wiring to gas piping, water piping, lightning conductor, or telephone ground wirings.
In the electrical wiring connection for RAS-7.0~12HNBRMQ1, do not connect the live wires (L1/L2/L3) to
the terminals N of the terminal block TB1. Otherwise, printed circuit board may be damaged.

Other manuals for Hitachi RAS-8.0HNBRMQ1

Related product manuals