10 Servicing
356
SMGB0077 rev.0 - 01/2013
Remove the screws -A- securing the drain pan and remove it.
N O T E
Whentting,sealthedrainhosegasketcorrectly.
10.7.6 Fan removal
Remove all screws -A- from the lower cover of the unit and
separate it.
Remove the electrical box cover Removal of the electrical box
cover.
Disconnect the fan motor.
N O T E
To disconnect and remove the fan motor, previously see the
chapter corresponding to the wiring diagrams in this Manual.
Remove the drain pan Removal of the drain pan.
Remove the wiring A- from the electrical box and release it from
the support -B-.
Remove the screws -C- on both sides of the fan.
C A U T I O N
Make sure the fan can be removed correctly, without the
risk of injuring anyone in the surrounding area.
The fan is heavy. Request the assistance of two operators
to hold the fan while it is being removed.
Remove the screws -A- on both sides of the fan and remove the
unit.
When tting, connect the fan motor connector to the electrical box
in line with the previous conguration:
Connector CN24 LSP (Low Static Pressure); (factory-supplied).
Connector CN25 HSP (High Static Pressure).
N O T E
Service cover fan assembly parts (runner, fan casing, fan
motor) must be performed once the fan assembly has been
removed from the unit.

Table of Contents