EasyManua.ls Logo

Hitachi RPC-6.0FSN2E - Removing Heat Exchanger

Hitachi RPC-6.0FSN2E
429 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Servicing
377
10
SMGB0077 rev.0 - 01/2013
10.9.10 Removing Heat Exchanger
D A N G E R
TURN OFF all power source switches.
C A U T I O N
• Recover the refrigerant from the unit before the work. After all the refrigerant is recovered, turn OFF all power source
switches.
• Makesurethattheunitwillnotbedamaged.Ifhavingdifcultyinperformingtheworkalone,theworkshallbetaken
by two people.
• Takespecialcarenottobeinjuredbytheheatexchangerns.
For RPK-(0.8-1.5)FSN(H)3M
1 Remove the power source wiring, the transition wiring and the wiring for the remote control switch.
2 Push the portion indicated by “PUSH” on the underside of the unit to release the catches at the lower part of the unit.
3 Remove the are nuts attached to the rear piping of the heat exchanger to disconnect the pipings. Then lift the indoor
unit up and draw it frontward to remove it.
4 Remove the front panel according to the “Removing Front Panel” chapter.
5 Remove the electrical box according to the “Removing Electrical Box” chapter.
6 Remove the drain pan according to the “Removing Drain Pan” chapter.
Piping Holder
Rear Piping of
Heat Exchanger
Connected
Pipings
Rear Side of Indoor Unit
7 Release 2 catches on the inside of the piping holder at the rear side of the indoor unit and remove the piping holder.
8 Remove 1 screw xing the right side of the heat exchanger. Then remove 2 screws xing the left side of the heat
exchanger.
Front Side of Indoor Unit (The gures above show the examples with the piping for heat exchanger removed.)
Catches for Piping Holder
Fixing Screw
for Heat Exchanger
Fixing Screw
for Heat Exchanger

Table of Contents