2  Unit installation
72
SMGB0077 rev.0 - 01/2013
C A U T I O N
In case that the thermistors supplied with the Dx-Interface are not long enough, please make sure that the length 
extension is properly done avoiding the sensing distortion and that the joint is properly insulated to avoid any 
electrical failure.
N O T E
When tting the thermistors, remember that they must be secured correctly by the special clamp, ensuring
the perfect contact between the pipe and thermistor. Cover it completely with insulation, like cork tape or pipe 
insulation, depending on the location. Replace them if damaged during maintenance work.
  
Thermistor installation example
1 Liquid / gas pipe thermistor (factory supplied)
2 Thermistor holder (eld supplied)
3 Thermistor lead wire (eld supplied)
4 Insulation (eld supplied)
1
2
3
4
C A U T I O N
The  thermistor  must  be  installed  properly  in  order  to 
avoid water onto the thermistor.
  
Typical installation location
A
Liquid pipe 
thermistor
Must be installed in the coldest liquid line 
point in the heat exchanger (prior the 
distributor).
B
Gas pipe 
thermistor
Must be installed as close as possible to 
the heat exchanger refrigerant outlet.