24
PMGB0126A rev.2 - 11/2006
ELECTRICAL WIRING
13.2. ELECTRICAL WIRING CONNECTION FOR OUTDOOR UNITS
  The electrical wiring connection for the outdoor unit as shown 
below:
  Table for Terminal Connection:
Wiring [connection (connection of terminals)]
Power supply
[O.U.-O.U.(L1-L1,L2-L2,L3-L3,N-N)]
[I.U.-I.U.(L1-L1,N-N)]
Operation [O.U--I.U.-I.U.(1-1,2-2)]
Remote controller R, CS-IV, IV-IV, A-A, B-B
  O.U.: Outdoor Unit, I.U.: Indoor unit
1.  Connect the power supply wires to L1, L2, L3 and NP, for the 
three phase units on the terminal board and ground wires to 
the terminals, in the electrical control box. 
2.  Connect the wires between the Outdoor and Indoor units, 
Master units only for twin system, to terminals 1 and 2 on 
the terminal board. If the indoor unit power source wires 
are connected with the outdoor unit connect also them to 
terminals L and N to the terminal board.
3.  Tightly secure the wires inside the outdoor unit with a band.
  Power source
  Operation wiring 
between outdoor and 
indoor unit
4.  Check the item below before turning ON the main switch. In 
case the power source is 415V (nominal voltage), change 
CN22 (connector) to CN21 of transformer (TF1) in the 
electrical control box as shown in fi gure below.
5.  Use factory supplied rubber bushes in order to protect wires 
from damages produced by hole edges  and 
13.2. SETTING OF DIP SWITCHES FOR OUTDOOR 
UNIT
Quantity and position of DIP Switches
  The PCB in the Outdoor Unit is operating with 5 types of DIP 
Switches, 1 Single Switch and 1 Push Switch. The location is 
as follows:
DSW1: Test Operation and Option functions 
settings
DSW2 Factory fi xed settings
DSW3: Capacity Settings
DSW4: Refrigerant Cycle no. settings
DSW5 Transmitting settings
PSW: Manual Defrost
  Press for Manual Defrost
■
■
■
■
■
■
■
Before shipment
Model 5HP 10 HP
Setting 
position
Nominal 
Operation
Before shipment
Before shipment
1 2
3
4
5
6
1 2
3
4
1 2
1 2
3
4
1 2
3
4
1 2
3
4