4  Electrical wiring
142
SMGB0077 rev.0 - 01/2013
Test runs
C A U T I O N
•  Be careful during the test runs, as some of the safety functions remain disabled: the units operate for two hours 
without switching off via the thermostat. The three-minute compressor protection is not enabled during the test.
•  Secure the rubber bushes to the panel using adhesive when the outdoor unit ducts are not used.
•  The compressor remains at a standstill during forced stoppage.
RPI-(8.0/10.0)FSN3E static pressure setting
RPI  units  have  been  provided  by  two  Static  Pressure  levels 
regulation depending on the installation requirements. High Static
Pressure  and  Low  Static  Pressure  (Std.  Factory  Setting) 
connectors are available into the Electrical Box.
Setting of Static Pressure shall be made by changing the Fan Unit 
connector.
•    A:  connector  CN24  LSP  (Low  Static  Pressure);  (factory 
supplied).
•    B: connector CN25 HSP (High Static Pressure).
To  do  so,  simply  replace  the  motor  power  connector  identied 
as CN24 (factory-connected for operation at low static pressure, 
LSP)  with  the  high-pressure  connector  CN25  (operation  at  high 
static pressure, HSP).
4.1.7  Electrical connection of RPIM units
Work prior to the electrical connection
1  Turn off the power supply switches before starting work and t the appropriate locks and safety warnings.
2  Wait 5 minutes after turning off the power supply switches.
3  Check that the fans on the indoor and outdoor units are at a standstill before starting work.
N O T E
•  Theelectricalpowerfortheunitmustinvolveaspecicpowerline,withanexclusivepowercontrolswitchand
residual current breaker, installed in line with local or national safety regulations.
•  Check that the electrical power line has enough capacity to supply the unit. Its length, the cable diameter and 
their protection (sleeve or jacket) must be appropriate for the unit.
•  For further information, always consider the current regulations in the country where the unit is to be installed.
 
C A U T I O N
•  Riskofre:cablesmustnevertouchtherefrigerantpipes,printedcircuitboards(PCB),sharpedgesorelec-
trical components inside the unit to avoid damaging them.
•  Loose  connection terminals  may  lead to  cable and  terminal overheating.  The unit  may operate  incorrectly, 
leadingtoariskofre.Checkthatthecablesarermlysecuredtotheconnectionterminals.